Installation Instruction

- 2 -

3)  Put MCCB on OFF and attach Base Assembly and MCCB to the enclosure panel 

using four NO.10-24UNC.
 Mounting screws are used to attach the circuit breaker at the lower mounting 
holes. Tighten to 150 in-lbs.(Refer to Fig 5 (a)).

3)  Ponga MCCB en OFF y adjunte Base Assembly y MCCB al panel de la caja 

usando cuatro NO.10-24UNC.

     Tornillos de montaje son usados para adjuntar el interruptor al hoyos de montaje 

inferior.Apriete a 150 pulg/lbs.(Refiera a Fig 5 (a)). 

4) Assemble the HANDLE ASS’Y on the door.  

Before the HANDLE ASS’Y assembling, please cut holes on panel to assemble 
the HANDLE ASS’Y. Tighten four screws(M4 x L25) to assemble the HANDLE 
ASS’Y through holes on the door. (Fig 6)

You can change operating angle, changing the HANDLE ASS’Y assembling 
holes position by 90 degree at same center point in clockwise direction only. 
Care should be taken not to damage the gasket. Align the gasket to match the 
holes to the handle Assembly. Install the gasket before attached before the 
Handle Assembly. (Fig 7)

4) Ensamble HANDLE ASSY en Panel Door. 

Antes de ensamblar HANDLE ASSY, prepare agujeros en el Panel como se 
muestra en la Fig 6. Después, utilice cuatro M4 X L25 Screws para instalar 
HANDLE ASSY en los agujeros. (Fig 6)

Cuando desee cambiar el ángulo de la instalación, puede poner agujeros a 90 
grados en el sentido del reloj. Sin embargo, verifique que no sea un obstáculo 
en la apertura y cerradura de Door. Tiene un Gasket.
En caso de ser usado en Panel, adhiera éstos al Door primero y después 
Handle. (Fig 7)