GIRARD TANKLESS WATER HEATER 

TECHNICAL SUPPORT INFORMATION 

FOR TECHNICIAN USE - NOT FOR END USER USE! 

 

IF THE RESULTS IN THE OPERATION ARE NOT SATISFACTORY

 

 
The Girard Tankless Water Heater burner will automatically adjust from 27,000 BTU to 34,000 
BTU depending on the incoming water temperature if the MODE Switch is set in the AUTO 
position. 
 
The Mode Switch is located inside the RV, it has two (2) positions; LOW and AUTO. LOW is 
27,000 BTU and AUTO is either 27,000 BTU or 34,000 BTU. If in AUTO Mode, the sensor will 
determine 

automatically

 whether to be on LOW 27,000 BTU or HIGH 34,000 BTU. The High/Low 

sensor is located inside the Water Heater compartment. It is a bimetal disc that looks like a 
limit switch and it is attached to the incoming water line, between the flow switch and the 
copper heat exchanger (back of compartment, lower left side). There may be a condition 
where this High/Low switch may not shift FROM Low to High at the appropriate time and/or 
temperature when on AUTO Mode. When this condition occurs the Water Heater may be in 
“LOW Mode” than in “HIGH Mode” so the water does not heat properly. This complaint most 
likely occurs either in the Spring or Fall seasons. 
 
In order to determine if this is a problem, we recommend that the tech does a manometer test 
on the Water Heater gas valve. The tap location is easily accessible from the outside in the 
Water Heater compartment. It is located near the bottom on the face of the Control Housing 
Panel (panel is on the left side). The gas valve is a dual BTU valve. When the Mode Switch is 
set in LOW Mode (27,000 BTU) the WCI pressure reading should be 6-7 water column inches. 
When the Mode Switch is set in AUTO Mode and the incoming water temperature is less than 
65 degrees (F) the unit should be in HIGH Mode (34,000 BTU) and the WCI pressure should be 
10 

– 11 water column inches. If this is not at these pressures we recommend the HIGH/LOW 

sensor be by-passed. The following procedure will make the MODE Switch High/Low rather 
than Auto/Low. This is acceptable since the Water Heater was originally approved without the 
AUTO Mode.  
BY- PASSING THE HIGH/LOW SENSOR 

 

OPEN THE WATER HEATER DOOR 

 

LOOK TO THE BACK LEFT OF THE WATER HEATER 

 

THE SENSOR IS LOCATED ON THE INCOMING WATER LINE, IT IS A BI-METAL 
SWITCH/DISC THAT LOOKS LIKE A LIMIT SWITCH. IT HAS TWO (2) BLACK WIRES 
ATTACHED TO IT WITH FEMALE SPADE TERMNALS. 

 

DISCONNECT BOTH BLACK WIRES AND ATTACH TOGETHER. YOU CAN EITHER; USE 
A DOUBLE MALE CONNECTOR, MAKE A DOUBLE MALE CONNECTOR WITH 2 MALE 
CONNECTORS AND A WIRE CONNECTED BETWEEN THEM OR CHANGE ONE OF THE 
FEMALE CONNECTORS TO A MALE CONNECTOR. 

 

WE DO NOT RECOMMEND THE RETAIL CUSTOMER PERFORM THIS CHANGE.  

 
ONCE THIS CHANGE IS COMPLETED THE INTERIOR MODE SWITCH “AUTO” SETTING IS 
NOW 

“HIGH MODE” AND IN LOW SETTING WILL STILL BE “LOW MODE”. NOTE - IN WARMER 

CLIMATES/CONDITIONS IT MAY BE NECESSARY TO PUT MODE SWITCH IN “LOW” MODE.

 