Order No. 2104 ..
4.2.5.4 Logic gate parameter
Description
Values
Comment
h
Logic gates
Number of logic gates
no logic gates
1 logic gates
2 logic gates
3 logic gates
4 logic gates
This parameter determines how many
logic gates are available.
h
Logic gate -> logic gate x (x = 1...4)
Type of logic operation
OR
AND
Exclusive OR
AND with feedback
This parameter defines which logic
operation is created by the gate. NAND
and NOR gates can be implemented by
inversion of the output.
Number of inputs
1 input
2 inputs
3 inputs
4 inputs
This parameter determines how many
inputs are available to each logic gate.
Number and type of
output objects
1 switching object
1 value object
2 switching objects
2 value objects
1 switching object and 1
value object
This parameter determines the type and
number of output objects of the gate.
Send output at
each input event
Change the output
This parameter determines when the
output objects are updated.
With "every event": the output object is
updated for every input event. If, for
example, a "1" is transmitted cyclically to
an input, then the output state is
updated in the same cycle and,
depending on the set transmission
behaviour, also transmitted if necessary.
With "Change the output": The output
object is only updated, and, depending
on the set transmission behaviour, also
saved if necessary, if the output
changes from "0" to "1" or from "1" to
"0".
Transmission behaviour
for logic 0
No telegram
Transmission without
delay
Transmission delay
The transmission behaviour of the gate
output is defined here for the state "0".
With "no telegram": No telegram is
generally transmitted for the output state
"0".
With "Transmission without delay":
During each update of the output state
(see "Send output at), a state "0" is
Page 166 of 171
Software "KNX CO2 sensor"
Parameters
Содержание CO2-Sensor