Figure 4 

Connection assignment of control cable 

RD, red: KNX+ 
BK, black: KNX– 
GN, green: input 1 
YE, yellow: input 2 
WH, white: input 3 
BN, brown: COM inputs 1...3 

3 Function 

System information 

This device is a product of the KNX system and complies with the KNX directives. Detailed 
technical knowledge obtained in KNX training courses is a prerequisite to proper 
understanding.  
The function of this device depends upon the software. Detailed information on loadable 
software and attainable functionality as well as the software itself can be obtained from the 
manufacturer´s product database. 
Planning, installation and commissioning of the device are carried out with the aid of KNX-
certified software. Full functionality with KNX commissioning software version ETS3.0d 
onwards.  
An updated version of the product database, technical descriptions and conversion programs 
and other auxiliary programs are available on our Internet website. 

Intended purpose 

Window actuator (Figure 1):  

Switching of electrically-driven Venetian blinds, awnings and similar blinds for AC 230 V  
mains voltage.  

Switching of electrothermal actuators  

Installation in appliance box to DIN 49073 

Connection with enclosed terminals 

Venetian blind actuator (Figure 2): 

Switching of electrically-driven Venetian blinds, awnings and similar blinds for 
AC 110...230 V mains voltage.  

Installation in appliance box to DIN 49073 

Connection with enclosed terminals 

Heating actuator (Figure 3): 

Switching of electrothermal actuators  

Installation in appliance box to DIN 49073 

Connection with enclosed terminals 

Product characteristics 

Depending on the equipment: 

Control of Venetian blinds, awnings and similar blinds  

Control of electrothermal actuators 

32572302 

10499188 I00 

20.05.2011 

3/8 

KNX/EIB 

Содержание 2164 00

Страница 1: ...off Do not connect any external voltage to the inputs since doing so may damage the device s and the SELV potential on the KNX bus line will no longer be available For parallel connection of several d...

Страница 2: ...2 Programming button and LED 3 Connection of mains and power cables Connection assignment power cables BK black connection L BN brown connection of Venetian blind up PK pink connection of Venetian bl...

Страница 3: ...s An updated version of the product database technical descriptions and conversion programs and other auxiliary programs are available on our Internet website Intended purpose Window actuator Figure 1...

Страница 4: ...tors only have the positions Open and Closed In PWM operation switch on and switch off during the drive s cycle time achieves an almost constant behaviour 4 Information for qualified electricians 4 1...

Страница 5: ...en the mains voltage and bus extension wires 4 mm Figure 6 o Connect the load Figure 7 Use the supplied sprung screwless terminals Flexible cable ends must be tin plated o Connect the device to KNX o...

Страница 6: ...tion software o Switch on the bus voltage o Assign physical addresses and load application software into the device o Note the physical address on the device label 5 Appendix 5 1 Technical data Window...

Страница 7: ...tions Ambient temperature 5 45 C Storage transport temperature 25 70 C Venetian blind output Contact type Switching current AC1 3 A Minimum switching current AC 100 mA Motors 230 V 600 VA Motors 110 V...

Страница 8: ...KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Power consumption KNX max 240 mW Connection mode KNX Connection terminal on control cable 5 2 Warranty The warranty is prov...

Отзывы: