11
Model: PO-VH & OVH-10
Installation
2-06. Fire Suppression System
Some local jurisdictions require Fire Suppression Systems be installed in all hoods, regardless of their use.
If yours is such a jurisdiction, please refer to the illustration instructions covered in this section.
Service of the fire suppression system is to be conducted by qualified fire equipment personnel. The
extinguishing system should be maintained as outlined in the Standard of Wet Chemical Extinguishing
Systems, NFPA 17A.
2-06.1.
General Installation
1.
This installation is to be made in accordance with the R-102 installation manual and in accordance
with all state and local codes.
2.
All pipe lengths to be field verified.
3.
These drawings may be used to secure approval from the authority having jurisdiction.
4.
It is necessary all pipe fittings and nozzles be wrench tightened and securely supported and all noz-
zles are properly aimed as indicated in the R-102 installation manual.
5.
The wire rope for the detector and remote pull station is to be installed by an authorized and factory
trained distributor or service representative.
6.
This installation is to be inspected, put into operation and certified by an authorized and factory
trained distributor or service representative.
7.
Electrical contractors and wiring for appliance shut-off to be provided by the electrical contractor.
8.
When installed as shown on the following drawings the system will comply with all relevant Ansul
installation, inspection, and maintenance manuals and shall comply with NFPA 96 when installed
and certified by authorized trained Ansul distributors in accordance with the R-102 manual.
9.
All agent distribution piping and detection conduit hood penetrations must be properly sealed in
accordance with NFPA 96.
Содержание OVH-10
Страница 3: ......
Страница 11: ...2 Model PO VH OVH 10 Introduction 1 4 Specifications 1 4 1 Overall Dimensions for PO VH UCM ...
Страница 12: ...3 Model PO VH OVH 10 Introduction 1 4 2 Overall Dimensions for OVH 10 UCM ...
Страница 22: ...13 Model PO VH OVH 10 Installation 2 06 4 Ansul System Plan Drawing See Section 2 05 6 for Parts List ...
Страница 27: ...Model PO VH OVH 10 Overview 18 3 01 Control Panel 6 5 4 3 2 1 Interlocking Start ILS Only ...
Страница 29: ...20 Model PO VH OVH 10 Overview 3 02 Filter Chamber and Exhaust Not Shown Optional 1 4 3 6 2 5 7 ...
Страница 33: ...24 Model PO VH OVH 10 Overview Notes ...
Страница 45: ...Notes Operation Filter Maintenance Model PO VH OVH 10 36 ...
Страница 53: ...44 Model PO VH OVH 10 Parts List 7 3 Filter Compartment PO VH Not shown UV Only 2 4 3 3 1 5 ...
Страница 57: ...48 Model PO VH OVH 10 Parts List 7 5 Filter Compartment OVH 10 Not shown UV Only 2 4 3 3 1 5 ...
Страница 59: ...50 Model PO VH OVH 10 Parts List Notes ...
Страница 61: ...52 Model PO VH OVH 10 Wiring Diagram 8 01 Wiring Diagram OVH 10 208 240 60 1 WIRING DIAGRAM P N 32804 I ...
Страница 63: ...54 Model PO VH OVH 10 Wiring Diagram 8 02 Wiring Diagram OVH 10 208 240 60 1 ILS WIRING DIAGRAM P N 33775 F ...
Страница 65: ...56 Model PO VH OVH 10 Wiring Diagram 8 03 Wiring Diagram OVH 10 208 240 60 1 UV WIRING DIAGRAM P N 90391 B ...
Страница 67: ...58 Model PO VH OVH 10 Wiring Diagram 8 04 Wiring Diagram OVH 10 208 240 60 1 UV ILS WIRING DIAGRAM P N 90392 A ...
Страница 69: ...60 Model PO VH OVH 10 Wiring Diagram 8 05 Wiring Diagram PO VH 208 240 60 1 WIRING DIAGRAM P N 35348 E ...
Страница 71: ...62 Model PO VH OVH 10 Wiring Diagram 8 06 Wiring Diagram PO VH 208 240 60 1 ILS WIRING DIAGRAM P N 33334 H ...
Страница 73: ...64 Model PO VH OVH 10 Wiring Diagram 8 07 Wiring Diagram PO VH 208 240 60 1 UV WIRING DIAGRAM P N 90393 B ...
Страница 75: ...66 Model PO VH OVH 10 Wiring Diagram 8 08 Wiring Diagram PO VH 208 240 60 1 UV WIRING DIAGRAM P N 90394 B ...
Страница 77: ...68 Model PO VH OVH 10 Wiring Diagram Notes ...