background image

After opening Fusible

Link is fitted onto pins

Open using Reset Key

Mode A

INSTALLATION AND REPLACEMENT
OF FUSIBLE LINK

BLADE DETAIL

INTERLOCKING ACTION OPPOSED BLADE
STAINLESS STEEL CONSTRUCTION

REMOVABLE RESET KEY

TYPE A STEEL
FASCIA GRILLE

AIRFLOW

GALVANISED STEEL 
FRAME CONSTRUCTION

Mode A
Fire Operated

3

Gilberts Smokegard Mode A has been designed
to allow the passage of ventilation air in normal
conditions and prevent the spread of 

FLAMES

in fire

conditions. It is available in a wide range of sizes
to cater for most air flow requirements and is
supplied with a door sleeve suitable for a 45mm or
54mm door or a wall sleeve suitable for a wall or
partition of specified thickness. The damper can
be suitably masked on both sides either with steel
type A grilles or aluminium non-vision type B
grilles.

O

PERATION

: The unit is activated by an integral

fusible link assembly. This assembly is under
constant spring tension to close the interlocking
blades and is only released, under fire conditions,
by the melting of the holding solder at 72°C which
allows the blades to close 

INSTANTLY

.

R

ESET

PROCEDURE

: Reset or initial setting is

accomplished by the insertion of a special key
through a hole in the inside frame (removal of
fascia grille is required for access). The key is
turned in a clockwise direction until the blades are
fully open and then, whilst holding the blades
open with the key, the fusible link is fitted over its
locating pins on the top pair of blades.

Содержание SMOKEGARD

Страница 1: ...struction Smoke or fire operated Stainless steel interlocking blades and side seals for maximum smoke retardation Galvanised steel frame Easy key reset 1 hour door 2 hour wall mounting fire ratings SMOKEGARD Door Wall and Partition Mounting Smoke and Fire Dampers ...

Страница 2: ...ith Stainless Steel Inter Locking Blades and Side Seals combining rugged construction with maximum Fire and Smoke retardation capabilities whilst the inter connecting Rack Blade operation feature is incorporated to ensure faultless precision Damper Operation Fire tested to BRITISH STANDARD 476 PART 20 1987 the units are 2 hour rated having been tested for 4 hours in a wall and 1 hour in a door Fiv...

Страница 3: ... suitable for a wall or partition of specified thickness The damper can be suitably masked on both sides either with steel type A grilles or aluminium non vision type B grilles OPERATION The unit is activated by an integral fusible link assembly This assembly is under constant spring tension to close the interlocking blades and is only released under fire conditions by the melting of the holding s...

Страница 4: ... HEIGHT 100mm in 100mm increments to 400mm Reverse sizes available only upon request LIST HEIGHT 92mm TYPE B GRILLE LIST HEIGHT 110mm LIST WIDTH 122mm LIST WIDTH 85mm LIST HEIGHT 84mm LIST WIDTH 80mm DOOR OR WALL SLEEVE WALL SLEEVE DEPTH VARIABLE PLEASE STATE REQUIREMENTS 29mm DAMPER SECTION THROUGH WALL DOOR TYPE A GRILLE 4 SMOKEGARD Door Wall and Partition Mounting Smoke and Fire Dampers ...

Страница 5: ...f fire were to reach the damper without such detection the unit would close regardless of external sources at 72 C by the action of its integral Electro thermal fuse Reset procedure Reset or initial setting which can be accomplished with the fascia grilles in place is achieved by the insertion of a special key through a hole in the grille and damper frame With the main 24V DC supply live the key i...

Страница 6: ...UT OUT H LIST SIZES AVAILABLE WIDTH 200mm in 50mm increments to 400mm HEIGHT 100mm in 100mm increments to 400mm Reverse sizes available upon only request TYPE B GRILLE LIST HEIGHT 144mm LIST WIDTH 122mm DOOR OR WALL SLEEVE WALL SLEEVE DEPTH VARIABLE PLEASE STATE REQUIREMENTS 29mm DAMPER SECTION THROUGH WALL DOOR LED KEY TEST HOLES MODE C ONLY 6 SMOKEGARD Door Wall and Partition Mounting Smoke and ...

Страница 7: ...STER MONITOR NOTE When damper is open yellow is VE When damper is closed blue is VE FROM SMOKEGARD YELLOW BLUE VE DC O R G O R G 240mm 240mm 87mm GI LBERTS POWER SUPPLY UNIT TYPE G12 MAINS INPUT 240 V A C l OUTPUT TO DAMPER 24 V A C l WARNING ISOLATE MAINS SUPPLY BEFORE ENTERING E N L MAIN POWER SUPPLY 240v AC 24v DC POWER OUT 240mm 240mm 75mm GI LBERTS UNINTERRUPTIBLE POWER SUPPLY E N L MAIN POWE...

Страница 8: ... C only The Mode C Smokegard has an integral LED to indicate the blade position of the damper open closed It fits into the right of the 2 circular apertures located on the top frame of the damper A key is also provided for local control or test To test the damper insert the key into the left of the 2 circular apertures NOTE Should access to the pcb be required for any reason ISOLATE the DC supply ...

Страница 9: ...TS Wall Mounting 1 Aperture to be cut into wall to match the damper size aperture dimensions detailed on page 5 2 The rear sleeve should now be fixed into the wall and secured with suitable screws and plugs if necessary through the flange 3 Mode A type Dampers which do not require an electrical connection can now be fitted from the front and secured with suitable screws and plugs if necessary thro...

Страница 10: ...PE B TYPE A SOUND LEVEL dbA GRILLE TOTAL PRESSURE N m 2 JET VELOCITY 200x100 250x100 300x100 350x100 200x200 400x100 250x200 300x200 350x200 400x200 300x300 350x300 400x300 400x400 200x100 250x100 300x100 350x100 200x200 400x100 250x200 300x200 350x200 400x200 300x300 350x300 400x300 400x400 TYPE B TYPE A GRILLE SIZES Nomogram Example Type Volume Sound Level Jet Vel Pressure Drop A 0 2 36 2 8 14 B...

Страница 11: ... from one face flange to the other through the door itself The combined assembly was placed vertically against one open side of a 1m3 furnace and then securely bolted to maintain an air seal between Test Results The duration of the test was 1 hour and only slight charring of the timber around the damper frame was apparent after this time At the end of the test the integrity and stability of both t...

Страница 12: ...tro magnet When the electro magnet is deenergised it allows the stainless steel pin to move forward thus disengaging the rack which moves immediately to the closed position shutting the blade pack For Mode A units a 72 C Fusible link is mounted on pivot brackets on the two opposed action blades On failure of said fuse link blades are allowed to move in opposed directions synchronised and driven by...

Отзывы: