INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

heater is installed using a float valve between the oil 

supply tank and the burner, and the supply tank is 

over nine (9)-gallon capacity, a valve operated by a 

fusible link shall be installed in the fuel line adjacent 

to and upstream from the float valve.

Oil Burner Installation

The installation of the oil burner must be performed 

by a qualified Oil Burner Technician. Before 

installing the oil burner, check the alignment 

between the burner and the combustion chamber. 

It is possible for the combustion chamber to shift if 

it is subjected to rough handling during transit. The 

end cone of the air tube must be centered to the 

accommodating passage provided in the design 

of the combustion chamber. Adjust as necessary. 

Failure to follow these instructions can result in 

property damage, personal injury or death.

The installation of the oil burner must be in accordance 

with all local codes or, in the absence of such codes, 

the latest edition of the CAN/CSA B139, Installation 

for Oil Burning Equipment, in Canada, and/or the 

latest edition of the  standard for Installation of Oil 

Burning Equipment, NFPA 31 in the United States.

Oil Filter

All fuel systems should include an oil filter between 

the fuel oil storage tank and the oil burner. When 

using an oil burner nozzle smaller than 0.75, install 

an additional 10 micron or better filter as close as 

possible to the oil burner.

Oil Burner Nozzles

The OG32 water heater is certified for multiple firing 

rates, ranging from 82,000 to 103,000 BTU/h. The 

OG50 models are certified for multiple firing rates, 

ranging from 97,000 to input 117,000 BTU/h. Refer 

to the water heater rating plate or Table 1 to deter-

mine the proper burner settings.

Wiring

This water heater uses an external electrical source 

for power. It must be electrically grounded in accor-

dance with all local codes or, in the absence of 

such codes, the latest edition of the CSA C22.1 

Canadian Electrical Code, in Canada, and/or the 

latest edition of the National Electrical Code, NFPA 

70, in the United States. Failure to properly ground 

this water heater can result in property damage, 

personal injury or death. 

This water heater is factory wired and requires mini-

mal field wiring. The water heater should be wired to 

a separate and dedicated circuit in the main electri-

cal panel. Although a suitably located circuit breaker 

can be used as a service switch, a separate service 

switch is advisable. The service switch is necessary 

if reaching the circuit breaker involves becoming 

close to the water heater or if the water heater is 

located between the circuit breaker and the means 

of entry to the furnace room. The water heater switch 

(service switch) should be clearly marked, installed 

in an easily accessible area between the water heat-

er and furnace room entry, and be located in such a 

manner to reduce the likelihood that it would be mis-

taken as a light switch or similar device

 (see Figure 10).

 

The power requirement is 120VAC, 60Hz.

Before lighting your water heater, check that all  

of the wires have been installed correctly 

(see 

Figure 11).

 Make sure that none of the wires are 

grounded, have split, or are broken. Verify that all 

wiring connections are properly secured, as there is  

a possibility that they have become loose dur-

ing transport. If any of the original wiring needs  

replacing, use only 18AWG-type, or greater wire that 

is approved for 221˚F (105˚C).

WARNING

AVERTISSEMENT

DANGER

Table 1

WARNING

AVERTISSEMENT

DANGER

OIL INPUT

Water Heater

Model No.

Burner Model No. Designation

Blast Tube

Insertion

Nozzle, Firing Rate @ psi

OG32

Beckett AF

3/4

0,60 - 70°A  82 000 BTU @ 100 psi

3/4

0,65 - 70°A   90 000 BTU @ 100 psi

3/4

0,75 - 70°A  103 000 BTU @ 100 psi

OG32

Beckett AF

3/4

0,70 - 70°A  97 000 BTU @ 100 psi

3/4

0,75 - 70°A  103 000 BTU @ 100 psi

3/4

0,85 - 70°A  117 000 BTU @ 100 psi

Man inst Oil -GI-IM001En-0211.indd   11

11-10-12   2:11 PM

Содержание OG32

Страница 1: ...ion may result causing property damage personal injury or death DO NOT STORE use gasoline or any other flammable vapours or liquids in the vicinity of this or any other appliance DO NOT USE gasoline crank case oil or oil containing gasoline DO NOT TAMPER with the unit or controls DO NOT LEAVE paper or rags close to the burner or the water heater WHAT TO DO IF YOU DETECT OIL Immediately call your o...

Страница 2: ...m Clearances 3 Combustion and Ventilation Air Supply 3 Requirements for Unconfined Spaces 4 Requirements for Confined Spaces Indoor Combustion and Ventilation Air 4 Requirements for Confined Spaces Outdoor Combustion and Indoor Ventilation Air 4 Requirements for Confined Spaces Outdoor Combustion and Ventilation Air 4 Air duct sizing 5 Louvers and Grilles 6 Corrosive Atmospheres 6 Venting 6 Chimne...

Страница 3: ...operate properly it must be supplied with an uninterrupted flow of clean combustion and ventilation air The area around the water heater must always be kept clean and clear of debris An inadequate supply of air to the water heater will produce a bright yellow burner flame caus ing sooting in the combustion chamber on the burner and in the flue tube This can result in damage to the water heater and...

Страница 4: ...es in the enclosure freely communi cating with interior areas that have in turn adequate infiltration from the outdoors Requirements for Confined Spaces Outdoor Combustion and Indoor Ventilation Air A water heater that is located in a confined space and that obtains its combustion air from outdoors and ventilation air from within the conditioned space of the building should be provided with two pe...

Страница 5: ... appliances in the enclosure b horizontal duct s as shown in Figure 7 with an equivalent length of less than 50 ft 15 m having a free flow area of not less than one 1 square inch per 2 000 BTU h 11 cm2 kWh of the total input of all oil fired appliances in the enclosure and c air openings that communicate directly with the outdoors as shown in Figure 6 having a free flow area of not less than one 1...

Страница 6: ...l chimney The chimney must be prop erly constructed and sized clean and free of soot creosote and obstructions able to generate suf ficient draft to evacuate the products of combustion outdoors and be lined with a tile or metal liner Inspect the chimney and make any repairs necessary before installing the water heater To prevent downdrafts the chimney flue should extend at least three 3 feet 1 m a...

Страница 7: ... in the United States Before installing the switch remember to DISCONNECT THE POWER SUPPLY to the water heater Failure to follow these instructions can result in property damage personal injury or death Installation 1 Install the pre assembled flue collar blocked vent switch assembly over the flue outlet on the water heater see Figure 9 2 Wire the switch to the aquastat on the water heater see wir...

Страница 8: ...is imperative that open flame is not applied to the inlet and outlet fittings as heat will damage or destroy the plastic lined fittings This will result in premature failure of the fittings which is not covered by the warranty 8 INSTALLATION INSTRUCTIONS FLUE COLLAR BLOCKED VENT SWITCH VENT PIPE FLUE OUTLET MANUAL RESET BUTTON FLUE COLLAR BLOCKED VENT SWITCH ASSEMBLY Figure 9 Figure 10 1 Flue coll...

Страница 9: ...r expands creating a pressure build up This is a natural function and is one of the reasons for install ing a temperature and pressure relief valve If the cold water supply line has a built in water meter check valve or pressure reducing valve a suitable expansion tank must be installed to prevent pres sure build up or water hammer effect Otherwise the warranty will be void see Figure 10 An indica...

Страница 10: ...y grounded in accor dance with all local codes or in the absence of such codes the latest edition of the CSA C22 1 Canadian Electrical Code in Canada and or the latest edition of the National Electrical Code NFPA 70 in the United States Failure to properly ground this water heater can result in property damage personal injury or death This water heater is factory wired and requires mini mal field ...

Страница 11: ... cleaning or sealing the system 3 If this water heater is to be used for space heating make sure that all safety codes are respected Pay special attention to safety valve pressure and expansion tanks Figure 11 L1 N Aquastat Fuse L1 N Gnd Oil Burner Junction Box Electrical Wiring Diagram For White Rodgers Aquastat Model 11B76 Black White Black Blue Black White L1 N Fuse Electrical Wiring Diagram Fo...

Страница 12: ...rom the water heater relief valve and premature failure of the heater due to expansion of the water during the heating cycle 7 Before acquisition of a water heater for space heating application it is necessary to have the area of intended use sized by a qualified technician This will ensure that an adequate water heating capacity will be available for both heating and potable water supply and that...

Страница 13: ...e blocking effect of louvers and grilles L Venting Is the flue baffle installed in the flue tube L Has the water heater been vented separately from all other oil fired appliances L Have all horizontal runs of vent pipe been installed with a minimum rise of 1 4 inch per foot 21 mm m of run L Water Piping Is the dip tube installed in the cold water inlet L Has a temperature and pressure relief valve...

Страница 14: ...ng combustion The warm up time is ideal for testing the oil pump pressure Water Temperature Regulation The higher the setting the greater the risk of scald ing Hot water can cause third degree burns in under one 1 second at 160 F 71 C in five 5 seconds at 140 F 60 C and in thirty 30 seconds at 130 F 54 C In households where there are children physically challenged individuals or elderly persons mi...

Страница 15: ...ir causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency After the burner has been firing for 10 15 minutes take a smoke sample with a Bacharach smoke sampler or other approved device Then take a sample of the flue gases and test for CO using a combustion analyser The smoke spot should not exceed Trace on the Bacharach Scale The water heater operates most effic...

Страница 16: ...xpectancy of the water heater is reduced where a water softener is introduced to fight hard water because the sodium salts added by a softener make this water extremely conductive In these conditions the anodes are consumed more rapidly and should be verified every year In cer tain water conditions the anodes will react with the water producing discoloured or smelly water The most common complaint...

Страница 17: ...y phone at 1 800 363 9354 To help serve you in a quick and efficient way always have the following information ready a Model number b Serial number c Date of installation d Where the water heater was purchased e Complete address where the water heater is installed f A description of the problem 1 2 3 4 5 7 8 6 9 10 I D Description 1 Aquastat 2 Oil burner 3 Brass drain valve 4 Overflow tube 5 Dip t...

Страница 18: ...amage caused by not having the water heater installed adjacent to a free flowing drain in the event of water leakage 10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times 11 If the heater has experienced the effect of thermal expansion due to excessive p...

Отзывы: