TWIN PIPE VENTING GUIDE
Total Equivalent Vent Length (Intake/outlet) for Twin Pipe three (3) inch (7.6 cm) PVC/CPVC
Maximum Vent Length
65 feet (19.8 m)
Termination Type
IPEX Concentric
Vent Kit
Snorkel
Termination
Side Wall Tee
Termination
Low Profile
Termination
Termination Equivalent Length
in feet (meters) (Already factored into the
straight pipe lengths below)
20 (6.1)
10 (3.0)
5 (1.5)
5 (1.5)
# of 90° Elbows (each: 5 equivalent feet)
Max. straight pipe vent length in feet (meters)
0
45 (13.7) **
55 (16.8) **
60 (18.3) **
60 (18.3) **
1
40 (12.2) **
50 (15.2) **
55 (16.8) **
55 (16.8) **
2
35 (10.7) **
45 (13.7) **
50 (15.2) **
50 (15.2) **
3
30 (9.1) **
40 (12.2) **
45 (13.7) **
45 (13.7) **
4
25 (7.6) **
35 (10.7) **
40 (12.2) **
40 (12.2) **
5
20 (6.1) **
30 (9.1) **
35 (10.7) **
35 (10.7) **
6
15 (4.6) **
25 (7.6) **
30 (9.1) **
30 (9.1) **
Table 11 - Natural Gas Units
Total Equivalent Vent Length (Intake/outlet) for Twin Pipe four (4) inch (10.2 cm) PVC/CPVC
Maximum Vent Length
100 feet (30.5 m)
Termination Type
IPEX Concentric
Vent Kit
Snorkel
Termination
Side Wall Tee
Termination
Low Profile
Termination
Termination Equivalent Length
in feet (meters) (Already factored into the
straight pipe lengths below)
20 (6.1)
10 (3.0)
5 (1.5)
5 (1.5)
# of 90° Elbows (each: 5 equivalent feet)
Max. straight pipe vent length in feet (meters)
0
80 (24.4) **
90 (27.4) **
95 (29.0) **
95 (29.0) **
1
75 (22.9) **
85 (25.9) **
90 (27.4) **
90 (27.4) **
2
70 (21.3) **
80 (24.4) **
85 (25.9) **
85 (25.9) **
3
65 (19.8) **
75 (22.9) **
80 (24.4) **
80 (24.4) **
4
60 (18.3) **
70 (21.3) **
75 (22.9) **
75 (22.9) **
5
55 (16.8) **
65 (19.8) **
70 (21.3) **
70 (21.3) **
6
50 (15.2) **
60 (18.3) **
65 (19.8) **
65 (19.8) **
Table 12 - Natural Gas Units
**Dip switch one (bank of eight (8) - TAN COLORED) off for lenths greater than or equal to twenty-one (21) feet (6.4 m).
DANGER
WARNING
CAUTION
AVERTISSEMENT
ATTENTION
Maximum vent lengths are specific to the fuel type of the tankless water heater. It is imperative when performing equivalent vent length
calculations, that the gas type be taken into consideration.