UK
SC130
SC130
UK
10
11
CONNECTIONS
Terminal
7-8
10
9
1
14
15
13
6
2
3
4
11
5
12
Abbrev.
FCA-FCC
PHOTO
COSTA
PH
12VDC
COM
ANT
DOWN
LAMP
NEUT
MOT COM
CLOS
COM
OPEN
UP
Description
OPEN-CLOSE (N.C.) Limit Switch
Photocell Input (N.C.)
Frame NC/8K2 Input (see DIP9)
12 Vdc for ACCESSORIES
power supply
Accessories Inputs-Outputs Common
ANTENNA CORE
(wire solded on circuit)
PEDESTRIAN Input (N.O.)
Courtesy light / Flashing light
Accessories Inputs-Outputs Common
START Input (N.O.)
Operation
Stop the motion in OPEN AND CLOSE or define
the beginning of the deceleration (see DIP 5).
If not used, set DIP 2 and 3 in ON.
If not used, put DIP4 in ON.
In OPEN irrelevant.
In CLOSE opens again.
If not used, set DIP1 in ON and DIP 9 in OFF.
In OPENING stops and releases the obstacle
for 2 s.
In CLOSING opens again.
In PAUSE operates as STOP and cancels the
automatic reclosing.
Protected by F1 5A.
Protected by F2 500mA resettable.
The gate opens for 7 s. A START makes open all
and interdicts the pedestrian.
Connect the flashing light or the courtesy light
between NEUT and LAMP (terminals 2-6) and
consequently set the DIP10.
If you use the courtesy light, connect the
flashing light (with its flashing circuit) between
MOT COM and CLOS (terminals 3-4).
Line 230Vac PHASE Input
Line 230Vac NEUTRAL Input
Motor COMMON
Motor CLOSE
Motor OPEN
DIP SWITCH SW1
DIP 5
DECELERATION disabled
DECELERATION enabled.
After the intervention of the limit switch, the motion
goes on for 1s in deceleration.
DIP
DIP 1
DIP 2
DIP 3
DIP 4
ON
FRAME Input disabled
OPENING LIMIT SWITCH Input disabled
OPENING LIMIT SWITCH Input enabled
CLOSING LIMIT SWITCH Input disabled
CLOSING LIMIT SWITCH Input enabled
PHOTOCELL Input disabled
PHOTOCELL Input enabled
OFF
FRAME Input enabled
DIP 8
See DIP 6 and 7
DIP 9
DIP 10
DIP 6-7
FRAME Input enabled as FRAME 8K2
FRAME Input enabled as FRAME NC
FLASHING LIGHT Output enabled as
FIXED COURTESY LIGHT (time = TL + TP)
FLASHING LIGHT Output enabled as
FLASHING LIGHT (time = TL)
Enables CONDOMINIUM LOGIC.
Automatic closing always enabled.
Operation in reply to START command:
• Gate close: OPEN.
• During opening: IRRELEVANT.
• Gate open: CHARGE TP AGAIN.
• During closing: OPEN.
See OPERATION LOGICS
TRIMMER
Trimmer
TL
TP
FV3
(on plug-in
module)
Description
Working Time
Pause Time
Adjustment 3 – 200s.
Turning clockwise, the pause time increases.
Force
Turning the trimmer anticlockwise on FORCE MODULE, force in closing is
increased, at every start there is is anyway an acceleration of 2 s at max. force.
In opening the force is always max. for the complete stroke and it is not
adjustable.
Operation
With jumper JP1 OPEN TL=7-120s.
With jumper JP1 CLOSE (default) TL=7-40s.
Turning clockwise, the working time increases.
OFF
OFF
STEP-BY-STEP
WITH STOP
Automatic closing disabled.
Operation in reply to a START
command:
• Gate close: OPEN.
• During opening: STOP.
• Gate open: CLOSE.
• During closing: STOP.
• After a STOP: It is necessary
a command and the motion starts
again in the opposite direction of
the previous motion.
Automatic closing disabled.
Operation in reply to a PEDESTRIAN
command:
• Gate close: OPEN for 7s.
• During opening: STOP.
• Gate open: CLOSE.
• During closing: STOP.
• After a STOP: It is necessary
a command and the motion starts
again in the opposite direction of
the previous motion.
DIP 6
DIP 7
Logic
START
PEDESTRIAN
OPERATION LOGICS
ON
OFF
DEAD MAN
If you keep pushed the button:
OPEN/CLOSE
If you keep pushed the button:
PEDESTRIAN