DIP SWITCH OPTION SETTINGS.
There are four DIP Switches located on the main control board (shown) that must be
positioned properly for your particular installation
A. DIP #1 OPEN DIRECTION.
The opening direction of the gate operator is determined by DIP#1.
DIP Switch # OFF Position
ON Position
1
Pull-To-Open (Factory Default):
Gate
is pulled to open into your property.
Push-To-Open Installation: Gate is pushed to open away from
your property.
B. DIP #2 ALARM WARNING.
The warning alarm is determined by DIP#2.
DIP Switch # OFF Position
ON Position
2
Warning Disabled: AUTOCLOSE and
initial gate movement alarm warning is
disabled. This does not disable the alarm
warning for consecutive obstruction as
required by UL325 safety standard.
Warning Enabled (Factory Default):
AUTOCLOSE and
initial gate movement warning is enabled.
C. DIP #3 MONITORED SAFETY DEVICES. Keep Switch To The Left (Factory Setting)
Unless Using
Monitored External Safety Devices Than Switch To The Right.
YOUR SYSTEM WILL NOT WORK IF SAFTEY MODE IS ON
AND YOU DO NOT HAVE MONITORED EXTERNAL
SAFETY DEVICES CONNECTED.
DIP Switch # OFF Position (FACTORY SETTING) ON Position
3
Patent-pending
SafeForce® Mode
(Factory Default):
Force output is
limited to ensure safe operation as
specified by Type C in UL325
requirement.
Monitored Safety Mode: Monitored safety devices required /
Compatible GHOST CONTROLS
®
safety devices only.
Monitored safety devices must be present and operate prop-
erly as specified by Type B1 or B2 in UL325 requirement. See
monitored safety device connection in the monitored photo
eye instructions manual for more details.
D. DIP #4 DOES NOT APPLY TO SINGLE GATES FOR DUAL GATE OPENING SEQUENCE.
Keep switch to the left.