BA_MA_STTV125M_EN_V1.2
12 / 24
Universal isolating amplifier TV125M / ST125M
Selection of signal type for in- / output
DIP-switches
On
Off
S1
Input configuration as voltage input
Input configuration as current input
S2
Output configuration as voltage
output
Output configuration as current output
Table 6 DIP-switches S1 and S2
Selection of live-zero
DIP-switches
On
Off
S3
Input configuration:
S1 = On: 0 … 10 V,
S1 = Off: 0 … 20 mA
Input configuration:
S1 = On: 2 … 10 V,
S1 = Off: 4 … 20 mA
S4
Output configuration:
S2 = On: 0 … 10 V,
S2 = Off: 0 … 20 mA
Output configuration:
S2 = On: 2 … 10 V,
S2 = Off: 4 … 20 mA
Table 7 DIP-switches S3 and S4
Configuration matrix
Configuration
S1
S2
S3
S4
Input
Output
1
Off
Off
Off
Off
4 … 20 mA
4 … 20 mA
2
Off
Off
Off
On
4 … 20 mA
0 … 20 mA
3
Off
Off
On
Off
0 … 20 mA
4 … 20 mA
4
Off
Off
On
On
0 … 20 mA
0 … 20 mA
5
Off
On
Off
Off
4 … 20 mA
2 … 10 V
6
Off
On
Off
On
4 … 20 mA
0 … 10 V
7
Off
On
On
Off
0 … 20 mA
2 … 10 V
8
Off
On
On
On
0 … 20 mA
0 … 10 V
9*
On
Off
Off
Off
2 … 10 V
4 … 20 mA
10
On
Off
Off
On
2 … 10 V
0 … 20 mA
11
On
Off
On
Off
0 … 10 V
4 … 20 mA
12
On
Off
On
On
0 … 10 V
0 … 20 mA
13
On
On
Off
Off
2 … 10 V
2 … 10 V
14
On
On
Off
On
2 … 10 V
0 … 10 V
15
On
On
On
Off
0 … 10 V
2 … 10 V
16
On
On
On
On
0 … 10 V
0 … 10 V
Table 8 DIP-switches, configuration
* Default setting