E36.0.01.6C-01
Installation and
Operating Manual GIA 0420 … - ex
page 12 of 20
button 2
button1
button 3
6
Selection of switching and alarm points
Only at option switching output
(GIA … ... - ex / S1):
Note:
All relevant switching and alarm points can be set at this menu.
(Preferred output position and delay of the output can only be set at configuration menu)
Depending on the selected output function different parameters have to be adjusted.
The configuration menu automatically skips parameters not needed for the selected output function.
Note:
menu cannot be called if output function is set off or at devices without option switching output
Follow these instructions to adjust switching and alarm points:
Press
button 1
for 2 seconds during actual value display,
„
1.on
“ or „
AL.Hi
“ is displayed.
Set parameter value with
button 2
and
button 3
.
Save the set with
button 1
, the parameter name is displayed again.
Proceed to the next parameter with
button 1
, the name of that parameter is
displayed.
If there is no key pressed within 60 seconds the configuration is cancelled.
The settings already entered are lost.
Parameter
Value
Description
Button 1
Button 2 and 3
1.ON
only at outP =
2P
Switch-on point of output 1
D,.LO
…
D,.X,
Value at which output 1 should be switched on.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
1.OFF
only at outP =
2P
Switch-off point of output 1
D,.LO
…
D,.X,
Value at which output 1 should be switched off.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
AL.X,
only at outP = A
L.F 1
Max-alarm point
AL.LO
…
D,.X,
Value, at which max-alarm should be triggered.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
AL.LO
only at outP = A
L.F 1
Min-alarm point
D,.LO
…
AL.X,
Value, at which min-alarm should be triggered.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
A.DEL
only at outP = A
L.F 1
Alarm delay
0
…
9999
The set value is the alarm delay in seconds.
The alarm case has to last for the set time to trigger the alarm.
After having set and confirmed the last point (depending on the selected output function) the configuration is done.
Press
button 1
one more time after the input of the last parameter to close the configuration menu. The devices
restarts (segment test).