page 9 of 10

 

 

10 Error Codes 

When detecting an operating state which is not permissible, the device will display an error code. 
The following error codes are defined: 

Err.1: 

Exceeding of measuring range 

Indicates that the valid measuring range of the device has been exceeded. 

Possible causes: 

- Input signal to high 
- Sensor shorted (at 0(4)-20mA) 

Remedies: 

- The error-message will be reset if the input signal is within the limits. 
- Check transmitter and device configuration (e.g. input signal). 

Err.2: 

Values below measuring range 

Indicates that the values are below the valid measuring range of the device. 

Possible causes: 

- Input signal is to low or negative 
- Current below 4mA 
- Sensor broken (at 4-20mA) 

Remedies: 

- The error-message will be reset if the input signal is within the limits. 
- Check transmitter and device configuration (e.g. input signal). 

Err.3: 

Display range has been exceeded 

Indicates that the valid display range (9999 digit) of the device has been exceeded. 

Possible causes: 

- Incorrect scale 

Remedies: 

- The error-message will be reset if the display value is below 9999. 

Err.4: 

Values below display range 

Indicates that display value is below the valid display range of the device (-1999 digit). 

Possible causes: 

- Incorrect scale 

Remedies: 

- The error-message will be reset if the display value is above -1999. 

Err.7: 

System error 

The device features an integrated self-diagnostic-function which checks essential parts of the device 
permanently. When detecting a failure, error-message Err.7 will be displayed. 

Possible causes: 

- Actual temperature is below / above the valid temperature range 
- Device defective 

Remedies: 

- Stay within valid temperature range 
- Exchange the defective device. 

Er.11: 

Value could not be calculated 

Indicates a measuring value, needed for calculation of the display value, is faulty or out of range. 

Possible causes: 

- Incorrect scale 

Remedies: 

- Check settings and input signal 

 

 

 

Содержание Greisinger GIA 010 N

Страница 1: ...esstechnik GmbH Hans Sachs Str 26 93128 Regenstauf GERMANY Tel 49 9402 9383 0 info greisinger de www greisinger de Universal display for 4 20mA or 0 10V transmitter GIA 010 N as of version 1 0 Operating manual GIA 0420 N WEEE Reg Nr DE93889386 ...

Страница 2: ... 20 mA output This design type doesn t need an auxiliary supply as it is supplied by the measuring current The GIA 010 is designed for the connection of any measuring transducers with a 0 10 V output The parameters and limit values can be input by buttons accessible at the rear side The operating range of the display device can be directly adjusted to the transmitter without any additional accesso...

Страница 3: ...ble conditions for a longer time In case of doubt please return device to manufacturer for repair or maintenance 5 The buttons at the rear side are necessary for the configuration of the device The device is ESD sensitive at this area The configuration must be done considering adequate ESD safety measures 6 Warning Do not use these products as safety or emergency stop devices or in any other appli...

Страница 4: ...tion of the display device in which case we cannot assume any warranty Mind for the GIA 0420 the maximum input current rating of 40mA under any circumstances 5 1 Terminal assignment GIA 0420 N GIA 010 N connection number GIA 0420 N GIA 010 N 1 signal supply 2 signal supply GND 3 inexistent signal 4 switching output switching output 5 switching output switching output 5 2 Connection example for opt...

Страница 5: ...al 4mA D X Upper display range limit display high 1999 9999 This value is displayed for input signal 20mA L Measuring range limit OFF deactivated Exceeding of the measuring range limit is tolerable as long as value is within measuring range p r t note ON ER active display error The measuring range limit is exactly bounded by the input signal When exceeding or short falling the input signal the dev...

Страница 6: ...ng of the configuration menu 1 DEL only at outP 2P Delay of switching function of output 1 0 0 999 9 The set value is the time in seconds the device waits at least after switching off output 1 to switch it on again 1 ERR only at outP 2P Preferred position of output 1 ON OFF If an error occurs the device switches output 1 to active on or inactive off AL X only at outP AL F 1 Max alarm point AL LO D...

Страница 7: ...er Value Description Button 1 Button 2 and 3 1 ON only at outP 2P Switch on point of output 1 D LO D X Value at which output 1 should be switched on Value has to be between upper and lower measuring range limit set at the be ginning of the configuration menu 1 OFF only at outP 2P Switch off point of output 1 D LO D X Value at which output 1 should be switched off Value has to be between upper and ...

Страница 8: ...cale in The displayed value is calculated according to the following formula Display measured value offset di Lo 1 slope adjustment 100 di Lo Example for offset and slope adjustment Connection of pressure transmitter The device displays without offset and slope adjustment at 0 bar 0 08 at 20 bar 20 02 From this calculated offset 0 08 slope 20 02 0 08 19 94 difference 0 06 ideal slope actual slope ...

Страница 9: ...uration e g input signal Err 3 Display range has been exceeded Indicates that the valid display range 9999 digit of the device has been exceeded Possible causes Incorrect scale Remedies The error message will be reset if the display value is below 9999 Err 4 Values below display range Indicates that display value is below the valid display range of the device 1999 digit Possible causes Incorrect s...

Страница 10: ...Switching point hysteresis freely adjustable Switching voltage max 28 V Switching current max 50 mA Please note the switching output is not short circuits protected Reaction time 250 ms Nominal temperature 25 C Working conditions 20 50 C 0 80 non condensing Connection via 2 or 3 pin screw type plug in terminal max wire cross selection 1 5 mm Housing glass fibre reinforced noryl front panel PC 24 x...

Отзывы: