Technical data
Voltage supply
UH:+250 VDC
Range of voltage supply:
+176 ... 288 VDC
Superposed AC peak-to-peak voltage:
12% @ rated voltage
6% @ voltage limits
Power consumption:
10 W max.
Bridging period on auxiliary voltage failure:
50ms to UH
24 VDC
Display memory
Number of indication memories
input 40
Number of indication memories
output 5
Number of group memories
1
Indication delay time
5 ms
Alarm contacts
Alarm relays for „tripping command dispatched” indication
2 NO contacts
Switching capacity make/break
20 VA
Switching voltage
250 VAC/DC
Permission current
0,1 A @ 250 VDC
Matrix
Number of columns (inputs)
40
Number of input taps
40
Number of input taps discontinuity
40
Number of input indication LED
40
Number of rows (outputs)
5
Number of output indication LED
5
Diode plugs
Type
GDS 621 ZS/20 sw (part. no. 674.212.002.00)
Max. reverse voltage
1000 V
Max. permissible current
1 A current flow direction from column (+) to row (-)
Insulation
Specification:
IEC 255-5
Max. voltage (input, output)
2,8 kV (eff.), 50 Hz
Max. over voltage
5 kV (peak), 1,2/50
μ
s, 0,5 J,
3 positive and 3 negative pulse within 5 sec. each
Climate conditions
Operation temperature
-5 °C to +55 °C
Storage temperature
-25 °C to +55 °C
Construction
Mechanical dimensions
19“, 6U W/H/D = 482,6 x 266.3 x 154,58 mm
Weight:
approx. 7 kg
Connectors
Clamp-connectors
max. wire section 2,5 mm²
__________________________________________________________________________________________________________________
GHIELMETTI AG,
Industriestrasse 6, CH-4562 Biberist, Schweiz - www.ghielmetti.ch - [email protected] -
T: +41 32 671 13 13 -
F: +41 32 671 13 14
___________________________________________________________________________________________________________________________________________________________________________________________________________
11/16
11/16