Technical data

Voltage supply

UH:+24 VDC

Range of voltage supply:

+18 - 36 VDC

Superposed AC peak-to-peak voltage:

12% @ rated voltage 6% @ voltage limits

Power consumption:

10 W max.

Bridging period on auxiliary voltage failure:

50ms to UH  24 VDC

Display memory

Number of indication memories

input 30

Number of indication memories

output 10

Number of group memories

1

Indication delay time

5 ms

Alarm contacts

Alarm relays for „tripping command dispatched” indication

2 NO contacts

Switching capacity make/break

20 VA

Switching voltage

250 VAC/DC

Permission current

0,1 A @ 250 VDC

Matrix

Number of columns (inputs)

30

Number of input discontinuity

30

Number of input taps

30

Number of input tap discontinuity

30

Number of input indication LED

30

Number of rows (outputs)

10

Number of output indication LED

10

Diode plugs

Type

GDS 621 ZS/20 sw (part. no. 674.212.002.00)

Max. reverse voltage

1000 V

Max. permissible current

1 A current flow direction from column (+) to row (-)

Insulation

Specification:

IEC 255-5 

Max. voltage (input, output)

2,8 kV (eff.),  50 Hz

Max. over voltage 

5 kV (peak), 1,2/50 µs, 0,5 J, 
3 positive and 3 negative pulse within 5 sec. each

Climate conditions

Operation temperature          

-5 °C to +55 °C

Storage temperature

-25 °C to +55 °C

Construction

Mechanical dimensions 

19“, 6U W/H/D = 482,6 x 266.3 x 154,58 mm

Weight:

approx. 7 kg

Connectors

Clamp-connectors 

max. wire section 2,5 mm²

11/12

11/12

Содержание 674.115.420.30

Страница 1: ...Tripping matrix for Generator Protection Systems GKV 10x30 621 AM EEaLDP 24VDC Part No 674 115 420 30 Operation Manual 1 12 1 12 ...

Страница 2: ...re or interfacing unauthorized mo dification operation outside of the envi ronmental specifications for the product or improper site preparation or maintenance Safety Considerations General This product and related documentation must be reviewed for familiarization with safety markings and instructions before operation This product has been designed and tested in accordance with inter national sta...

Страница 3: ...gnals to tripping modules Each of the 30 column signals may be connected twice by tap connectors High reliability diode plugs black hand le are used for programming the matrix the reliability being attained by generous over rating with respect to forward current and reverse voltage The diode plugs are inserted from the front and enable any vertical column sig nals from the protection relays to be ...

Страница 4: ...ndicating outgoing switching pulse LED Test To test if all LEDs work Reset Of all LEDs Pin Park 2 rows by 430 pin parks each Diode Plug Test Unit Type GDS 621 ZS 20 sw 674 212 002 00 If the LEDs light after inserting into the left position and do not light after inserting in the right position then the diode plug is o k Power ON indication LED 4 12 30 input signal discontinuity interupt the input ...

Страница 5: ...ripping Matrix Input screw mount connectors max 30 input signals Output screw mount connectors max 10 output signals Auxiliary output screw mount connectors Input signal tap screw mount connectors max 30 input signals 5 12 ...

Страница 6: ...__ _________ ________ _______ _______ Chassis 0V 24 Reset 24 LED 24 5VDC 5VDC Remote Rack Ground VDC VDC VDC Power Power Signal Lamp Monitoring Failure Power Remote Remote Supply Reset LED Test Auxiliary output screw mount connectors ...

Страница 7: ...Schematic diagram of the Tripping Matrix 7 12 ...

Страница 8: ...Front view 8 12 ...

Страница 9: ...Back view 9 12 ...

Страница 10: ...Side view 10 12 ...

Страница 11: ...r of columns inputs 30 Number of input discontinuity 30 Number of input taps 30 Number of input tap discontinuity 30 Number of input indication LED 30 Number of rows outputs 10 Number of output indication LED 10 Diode plugs Type GDS 621 ZS 20 sw part no 674 212 002 00 Max reverse voltage 1000 V Max permissible current 1 A current flow direction from column to row Insulation Specification IEC 255 5...

Страница 12: ...12 12 ...

Отзывы: