GFS FWS-NT 2 Скачать руководство пользователя страница 2

GfS

 

Sicherheit an Türen

771443_FWS-NT 2_0518    

Subject to technical changes

 

INSTALLATION

1.   Remove the protective cover from the emergency exit switch.

2.   Loosen the two screws on the upper housing.

3.   Remove the connectors from the chassis. Mount the chassis near the door. 

Make sure the emergency exit switch is accessible to wheelchair users  

and children. The emergency exit switch has to be installed at a height of  

850 − 1200 mm.

4.   Wire the emergency exit switch according to the instructions. Secure the 

wires with cable ties. 

5.   Put the connectors onto the terminal.

6.   Place the upper housing on the base housing, insert the screws and fasten 

them. Make sure that you do not squeeze any cables!

7.   Place the adhesive picto above the emergency exit switch.

8.   Put the protective cover back in place. 

Reset emergency exit switch

When pressing the emergency exit switch the end position is locked. The relay 

opens permanently. To reset the emergency exit switch, follow these steps:

1.   Remove the protective cover of the emergency exit switch

2.   Turn the red emergency knob in direction of the arrow. The red emergency 

knob is released and jumps back in its original position.

3.   Put the protective cover back in place. The emergency exit switch is ready for 

use again.

CONFORMITY 

This product complies with the main requirements of the R&TTE guideline 

1999/5/EG. The certificate of conformity you may request from your supplier. 

DISPOSAL 

Dispose an obselet GfS Door Terminal at a colleting point for electronic waste or 

at your supplier. Dispose the packaging material at a paper col lecting point for 

paper resp. plastic. You may not dispose an obsolte de vice in the general garbage.

 

WARRANTY 

Within the legal warranty, we intend to repair or replace all defective devices 

whether the dammage is caused by a material or a manufacturing failure. The 

warenty expires after a third-party repair. 

SERVICE 

In case of a system failure or a defective GfS Door Terminal, please contact the 

following address: 

GfS – Gesellschaft für Sicherheitstechnik mbH

Tempowerkring 15 ∙ 21079 Hamburg ∙ Fon 040-79 01 95-0 ∙ Fax 040-79 01 95 11 ∙ www. gfs-online com ∙ [email protected]

SPECIFICATIONS
Certified

 

EN 60947-5-1

Power supply

 

12 V–24 V/DC 

Degree of protection

  

IP 20 

Output

  

1x opener NC

Accesories

 

1x opener NC (771 425) for FWS-02 or

 

1x closer NO (771 426) for alarm signal

Status indication 

 

1 LED red/green

Max. contact load

 

DC 30 V/0,5 A 

Operating temperature

  − 20° C to +60° C 

Dimensions

 

90 x 120 x 80 mm 

Weight

 

ca. 0,35 kg 

TERMINAL BOARD WITH RELAY

1  

Opener 1 − NC

2  

Opener 1 − NC

3

4  

Additional opener − NC/closer − NO 

5  

Additional opener − NC/closer − NO

6

7  

Switched minus from FWS-02 (Emergency Exit Control Unit)

8  

Backlight lamp + 24 V

9  

Backlight lamp – 24 V

10

11

12  GND

Certified emergency exit switch FWS-NT 2 with relay 

Art. No. 771 443

Safety instructions!

The certified emergency exit switch may only be installed acc. to the 

specifications of the assembly instruction.

•   Respect max. current draw and operating voltage
•   Non working emergency exit switches have to be examined by 

the manufacturer

•   Do not modify the emergency exit switch without the permis-

sion of the manufacturer

Secure the wires with cable ties!
In particular, it should be noted that the wires of terminals 1 and 2 as 
well as 4 and 5 have to be secured separately in order to prevent 
unintended shifting of these wires to + 24 V. 

The terminals 9 and 12 of the 

FWS-NT 2 are bridged internally and connected to the terminal 6 of the 

emergency exit control unit FWS-02 (if available).

1

2

6

10

4

8

12

3

7

11

5

9

FWS-02 (24)

FWS-02 

(21)

FWS-02 

(19)

FWS-02 

(20)

FWS-02 

(18)