31
Reading out W SD door-modul e data
Reading out WSD door-module data
WSD door-module data
(Only activated at taught-in WSD door-module,
Displaying of missing data is done by „-.-.“)
Data indicated alternately
1. Version of master radio module
2. Type of safety edge
„0.0.“ = none
„0.1.“ = 1k2
„0.2.“ = 8k2
„0.3.“ = optic
3. Door safety switch
„0.0.“ = inactive
„0.1.“ = active
4. Battery voltage
5. Assigned / selected communication channel
6. Signal quality ranging from 0% - 99%
8
Safety devices
X2: Input, safety edge
The door control automatically detects three different safety edges to protect the closing
movement of the gate wing.
Electrical safety edge,
Pneumatic safety edge,
optical safety edge system.
Important!
▶
Connect safety edge systems in accordance with EN 12978
▶
Check position of S5 pre-limit switch on the safety edge (only for NES)
When the door is opened > 5cm, a reversing
must be executed if the safety edge has been activated
"Hold-to-run" door operating mode can always be used should the safety edge be
defective