Completing commissioning / inspection
Check the following components and then install all covers.
Gearbox
Check the drive unit for loss of oil (a few drops can be neglected). Protect the output-shaft
permanently against corrosion.
Mounting
Check that all connection elements (consoles, torque mounts, screws, locking rings, etc.) are
secure and in proper condition.
Electrical wiring
Check the connection cables and cabling for damage or crushing. Check that the screw
connections and plug connections are fitted properly with a good electric contact.
Emergency manual operation
Check the function with the power disconnected. Perform the check only between the final
limit positions.
Limit switch
Check the final limit positions by opening and closing fully. The safety area must not be
approached.
Drive unit
Note!
Engage a qualified engineer to check the drive unit annually
Apply shorter inspection intervals for doors that are operated frequently
Observe the applicable regulations and standards