Settings motor current monitoring 

The current monitoring function monitors the motor current. If the motor 
current is higher than the pre-set value, an error is reported and the actuator 
will remain in place. The setting is done via the left BCD switch marked 
“CurrentMon.” on the PCB. 
 

Motor

 C

ur

ren

t Mon

ito

ri

ng

 [mA]

 

BCD 

EA25 

EA45 

EA120 

EA250 

0  

25 

25 

50 

50 

100 

300 

300 

400 

150 

350 

400 

500 

200 

400 

500 

600 

250 

450 

600 

700 

300 

500 

700 

800 

400 

600 

800 

1000 

500 

700 

900 

1200 

600 

900 

1000 

1500 

9 (factory setting) 

700 

1100 

1200 

1800 

 

 

7

 

Error message 

An error can trigger the following: 

 

The 7-segment display on the main board illuminates; see illustration 
below. If the positioner PCB is installed, the respective LED lights up red on 
the BCD switch, if its set value is exceeded. 

 

The ready-to-operate signal will be off (terminals 5,6 NO contact) 

 

LED flashes yellow (except in case of power outage) 

 

 

 

Assignment of error codes for error messages 

If the positioner PCB is installed, the following error codes can be displayed: 

 

Error code 

Description 

Signal „Ready-
to-operate“ 

EA response 



Setpoint error 

 

None 



Actual value error 

 

None 



Setpoint reversed polarity 

 

None 



Actual value reversed 
polarity 

 

None 



Setpoint short circuit  

 

None 



Actual value short circuit 

 

None 



Actuator has run into 
engine current limit 

No 

Stops 

 

* If the feedback is not connected the error LED will show an actual value error. This can 
be avoided by placing a resistor (supplied) between terminal 5 and 6 of the positioner. 
Remove the resistor to use the feedback. 
 
For further error codes of the main board, see instruction manual of the electric actuator 
type EA 25-250. 
 
 
 
 
 
 
 
 

 
 

Acknowledge error message 
Check the cause of fault, if necessary, carry out relevant maintenance. 

 

 

 

The message can be eliminated while the supply voltage is still connected 
or the actuator is briefly disconnected from the mains voltage (does not 
work with cycle monitoring). 

 

Error can be acknowledged via the „SET“ button on the main board.

 