Settings motor current monitoring
The current monitoring function monitors the motor current. If the motor
current is higher than the pre-set value, an error is reported and the actuator
will remain in place. The setting is done via the left BCD switch marked
“CurrentMon.” on the PCB.
Motor
C
ur
ren
t Mon
ito
ri
ng
[mA]
BCD
EA25
EA45
EA120
EA250
0
25
25
50
50
1
100
300
300
400
2
150
350
400
500
3
200
400
500
600
4
250
450
600
700
5
300
500
700
800
6
400
600
800
1000
7
500
700
900
1200
8
600
900
1000
1500
9 (factory setting)
700
1100
1200
1800
7
Error message
An error can trigger the following:
The 7-segment display on the main board illuminates; see illustration
below. If the positioner PCB is installed, the respective LED lights up red on
the BCD switch, if its set value is exceeded.
The ready-to-operate signal will be off (terminals 5,6 NO contact)
LED flashes yellow (except in case of power outage)
Assignment of error codes for error messages
If the positioner PCB is installed, the following error codes can be displayed:
Error code
Description
Signal „Ready-
to-operate“
EA response
Setpoint error
None
Actual value error
None
Setpoint reversed polarity
None
Actual value reversed
polarity
None
Setpoint short circuit
None
Actual value short circuit
None
Actuator has run into
engine current limit
No
Stops
* If the feedback is not connected the error LED will show an actual value error. This can
be avoided by placing a resistor (supplied) between terminal 5 and 6 of the positioner.
Remove the resistor to use the feedback.
For further error codes of the main board, see instruction manual of the electric actuator
type EA 25-250.
Acknowledge error message
Check the cause of fault, if necessary, carry out relevant maintenance.
The message can be eliminated while the supply voltage is still connected
or the actuator is briefly disconnected from the mains voltage (does not
work with cycle monitoring).
Error can be acknowledged via the „SET“ button on the main board.