Commissioning
Seite 36 von 64
Rev.: 11013802-2
4.4
Press the ‘M’ button, hold for two
seconds, and release again.
Count:
Twenty-one, twenty-two
The control system starts automatically
with
a commissioning routine.
Status-No.:
04. / Selftest
Check the unit for leaks at the same
time!
Decimal point on the display flashes
LED: green lights up
Duration approx. 3-4 min.
DO NOT leave the limescale
conditioning system unattended and
DO NOT unplug it as long as the
decimal point is flashing!
While the decimal point is flashing the device is
automatically filling up with water and all the
important functions are being checked:
1.
Valve piston drive
2.
Position indicator
3.
The slider is moved into the
backflushing position,
the device is
automatically aerated
4.
Heating element for thermal
disinfection
5.
Check the dimensioning of the drain!
Flushing is repeated several times
After the self-test, a TD is automatically started.
Status no.:
02. / thermal disinfection
DO NOT leave the limescale
conditioning system unattended and
DO NOT unplug it as long as the
decimal point is flashing!
Содержание JRG Coral force 5000
Страница 2: ...Seite 2 von 64 Rev 11013802 2 ...
Страница 5: ...Foreword Rev 11013802 2 Seite 5 von 64 ...
Страница 23: ...Installation Rev 11013802 2 Seite 23 von 64 7 1 Prepare the JRG Coral force for installation A B ...
Страница 24: ...Installation Seite 24 von 64 Rev 11013802 2 A ...
Страница 26: ...Installation Seite 26 von 64 Rev 11013802 2 ...
Страница 27: ...Installation Rev 11013802 2 Seite 27 von 64 ...
Страница 62: ...Spare parts and service set Seite 62 von 64 Rev 11013802 2 ...
Страница 63: ...Spare parts and service set Rev 11013802 2 Seite 63 von 64 ...