Configurable outputs
12.1.2 Fault
à
The function is used for fault messages, e.g. to a customer building control centre. The contact closes or opens
if the control determines a fault, see chapter 28 “Error messages”.
à
Set the parameters with:
à
DPS: Set
a1
to
0 2
(Fault NO contact) or to
0 3
(Fault NC).
à
ST220: Set "PA1 function" to "Fault NO contact " or "Fault NC".
1
Building control centre (provided by customer)
2
Signal input
PA
55
PA1A
56
PA1B
2
1
12.1.3 Fault indication for MPS
The function is used to switch the fault LED at the MPS. The contact closes if the control determines a fault, see
chapter 28 “Error messages”. When maintenance is due, the output is connected cyclically, and the fault LED on
the MPS flashes.
à
For connection see chapter 16.1 "Programme switch", "Mechanical programme switch (MPS)".
à
Set the parameters with:
à
DPS: Set
a1
to
0 4
(MPS fault).
à
ST220: Set "PA1 function" to "MPS fault".
12.1.4 Warning signal
à
The function is used to cyclically switch on/off a customer signal device while the door is opened or closed.
à
Observe the maximum permissible total current draw of the control.
à
Set the parameters with:
à
DPS: Set
a1
to
0 5
(Warning signal).
à
ST220: Set "PA1 function" to "Warning signal".
1
24 V DC signal transmitter supplied on the drive side.
55
PA1A
56
PA1B
PA
1
GND
2
24 V
1
12.1.5 Electric strike
The electric strike function is not permissible if the drive is used for the fire-protection area (Powerturn F, F/R, F-IS
with fire protection kit).
à
An additional electric strike can be connected to the configurable output PA1.
à
Observe the maximum permissible total current draw of the control.
à
Set the parameters with:
à
DPS: Set
a1
to
0 6
(Electric strike).
Set
TO
to the connected electric strike type, see chapter 27.5 "Service menu DPS".
à
ST220: Set "PA1 function" to "Electric strike".
Set "Electric strike type" to the connected electric strike type, see chapter 27.3 "Service menu ST220".