TS 5000 R BG
GB 5
Mounting and securing
Use cable protection for the 230 V cable when leading through plaster.
Insert the 230 V cable/cable for additional connections protruding from the wall through the
respective openings of the smoke switch housing.
Fig.: 6.3.1
X
Guide 230 V power cable through smoke switch housing and shorten to approx. 80 mm (
1.
).
X
Route 24 V cable of electrical hold-open device in the upper guidance of the smoke switch
housing (
2.
).
X
Align smoke switch housing and screw it firmly to moving-leaf guide rail and frame (
3.
).
Fig.: 6.3.2
Fig.: 6.3.3
X
Fuse the on-site mains connection with a B10 fuse.
X
Place (
2.
) the mains cable provided on site on the terminal and connect (
3.
).
X
Place (
4.
) the 230 V supply line of the power pack starting from the terminal and stow away extra length in the
power pack.
X
Close and screw on cover of smoke switch housing (
5.
).
X
Place 24 V output cable into the inside of the smoke switch housing (
6.
). Protect both 24V cables with foam
lining against falling off (
7.
).