Terminal diagram

Jumper

Position

Meaning

J1, J2

  

1    2    3    4

No indirect release, built-in power supply for safety circuit

(Factory setting: Jumper on terminal X107 between 7 and 8 set)

1    2    3    4

Indirect unlocking, external power supply for safety circuit

connected to terminals 7 and 8 of terminal strip X107

J3

   

1    2

CAN terminating resistor set

(factory setting)

   

1    2

CAN terminating resistor not set

Notes about the terminal diagram

6.2 

   

If no locking element is to be connected (door monitoring), the following possibilities exist:

Use a door control unit without emergency switch (TZ322)

 

à

Connect door control unit with emergency switch to terminal field X106 as follows:

 

à

Connect a 10K resistor between terminals 5 and 6

 

à

Connect a jumper between terminals 5 and 14 or an external Locked signal

 

à

Connect a door contact or fit a bridge between terminals 2 and 15

 

à

  

Connecting locking elements:

Make sure that they are connected correctly. If they are connected with reversed polarity, the controller can 

become damaged. If the controller’s relay “chatters” and the LEDs are flashing on and off, isolate the door control 

unit from the mains immediately and check the connections.

The notes apply for the following terminal diagram of the various versions of the TZ320.
1) 

A mains fuse is provided by the owner.

2) 

GEZE PSU for TZ320N UP = NET220. 500 mA max. 350 mA for peripherals 

 

 

GEZE PSU for TZ320N AP = NT19.2-24. 750 mA max. 650 mA for peripherals

 

Spatially separate primary and secondary side.

3) 

With the TZ320 the PSU is fitted outside the door control unit.

4)   TZ320N UP: Protection class II (do not connect PE conductor)
 

TZ320N AP: Protection class I with PE conductor testing according to VDE0100.

5) 

Jumper set by default.

 

For indirect unlocking, remove jumper and change jumper position J1 and J2.

6) 

Factory setting:

 

Contact closes on alarm. 

 

Contact is open on mains failure.

 

Observe total power consumption.

7) 

On the surface-mounted version the screw terminal is fitted to the mounting plate.

8) 

Contact is closed when door is closed.

9) 

When a GEZE alarm bell or siren is fitted, a jumper must be set.

Содержание SecuLogic TZ320

Страница 1: ...1 GEZE SECULOGIC TZ320 Emergency Exit System Door Control Unit GB Installation and Commissioning Instructions with Terminal Diagram Brief instructions...

Страница 2: ...6 4 Unlocking through BMA GMA or RWA 17 6 5 Key switch SCT221 SCT to temporary unlocking 17 6 6 Key switch SCT320 for external control unlocking locking temporary unlocking and acknowledging alarms 17...

Страница 3: ...s along escape routes should be inspected annually by a specialist The specialist X X must issue a certificate verifying the periodic inspection which the owner must submit to the building inspec tora...

Страница 4: ...ding to VDE 0833 surface mounted cables in steel conduit For flush mounted cabling flush mounted sockets depth 62 5 mm at a mounting height of 850 mm from upper edge of floor and up to 1200 mm for the...

Страница 5: ...ation and assembly Fit the terminal blocks to the back of the door control unit X X Fit jumpers according to the terminal diagram X X Fit the door control unit X X Fit the green adhesive frame X X Tes...

Страница 6: ...ht of emergency button 850 mm 1200 mm from floor X X surface 850 1200 Take off the mains connection cover X X Connect the 230 V cable to the screw terminals of the PSU and refit the cover X X Connect...

Страница 7: ...inder 40 mm 30 10 Eight way adjustable When the plant is in operation set it into service X X mode To do this turn key to left for ten seconds Right LED lights up green Take housing off the wall brack...

Страница 8: ...e any action for three minutes or in the Service menu select End service mode X X The door control unit is then in its normal state again Connecting service terminal ST220 with door control unit 4 2 3...

Страница 9: ...is locked again automatically and the pre alarm is reset Door alarm 4 4 5 If the pre alarm time is exceeded the door alarm is triggered This must then be reset with the built in key switch or with a n...

Страница 10: ...t for about one second X X LED 1 lights up green The door is unlocked Locking the door When the system is unlocked the locking elements are enabled and the door can not be be opened Turn the key to th...

Страница 11: ...e emergency button to the right X X The emergency button returns to its normal state Refit the cover X X Acknowledge the alarm X X Acknowledge alarm 5 3 2 Precondition The alarm cause has been elimina...

Страница 12: ...d twice Bus system address assigned more than once Change CAN address X X Invalid date time Invalid date or time value Correct data in service menu X X Reading out alarm messages 5 5 Misuse of the sys...

Страница 13: ...ugh built in emergency button Reset door control unit emergency X X button SK failed NT opener failed NC contact of built in emergency button failed Locking element not connected Rectify fault X X Che...

Страница 14: ...us communication 45 CAN L GEZE bus communication 42 RS485 A communication with KL220 TAN220 41 RS485 B communication with KL220 TAN220 X105 Black terminal field 2 24 V DC 12 Key switch lock temporary...

Страница 15: ...they are connected with reversed polarity the controller can become damaged If the controller s relay chatters and the LEDs are flashing on and off isolate the door control unit from the mains immedi...

Страница 16: ...s 41 RS485 B X107 green terminal strip 24VDC 2 Directunlocking 7 1 GND 8 Indirectunlocking Powersupplyunit Screwterminal X102 PlugforGEZE keyswitchor BK RD RD BN BU 6A 2 1 BN BU L1 N GN YE PE 4 5 NO C...

Страница 17: ...contact for unlocking set the input to High Active Key switch SCT221 SCT to temporary unlocking 6 5 Brief unlocking input 24 V DC orange terminal strip SCT No 117996 024467 UP AS500 SCT No 117996 0244...

Страница 18: ...ing Doorclosed 24VDC Input1 short termrelease 24VDC Input3 firealarmsystem Input2 short termrelease Temporary unlocking through button key switch Access control Door contact Powersupplyunit Ribboncabl...

Страница 19: ...h is working correctly Locking through key switch is working correctly Forced locking through EMA working Feedback from magnet and or door opener working correctly Additional door contacts working cor...

Страница 20: ...est H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla C Comerc 2 22 Nave 12 08980 Sant Feliu de Llobregat Barcelona Tel 34 0 9 02194036...

Отзывы: