Settings
9
Settings
9.1 Setting the closing force
à
The closing force must be set at the power storage device for all installation types in such a way that the door
closes in a secure manner when in the de-energised state. (For types of installation see chapter 5.3).
à
The spring force may only be changed when the door is closed.
à
The closing force must be set in accordance with
DIN 18263-4
depending on the door width, use as a fire pro-
tection door and the assignment of EN classes (see next page).
à
Measurement of the closing force is only possible in a de-energised state.
X
Before measurement, activate the door at least once.
à
For information regarding the setting of the spring force, see the table below.
X
Use an Allen key (size 5) to set the adjustment screw (1) to the desired spring force.