is the thermal element adjustment dial and is used to set the rated current to match the conductor rating.
I
R
can be set between 0.63 and 1.0 times I
n
.
- I
i
is the magnetic element adjustment dial and is used to set the short circuit tripping threshold to suit the application. It is fixed on 160A frame.
MSX 160c MCCB Adjusting Dials
MSX 250c MCCB Adjusting Dials
Models, ratings and settings
ADJUSTMENT DIALS
Model
Breaking capacity
Rated current I
n
(A)
Magnetic trip current I
i
(A)
MSX 160c
16 kA
25, 40
600
63, 80
1000
100, 125
1500
160
1600
25 kA
25, 40
600
63, 80
1000
100, 125
1500
160
1600
MSX 250c
16 kA
160
5 - 13 x In
250
5 - 11 x In
25 kA
160
5 - 13 x In
250
5 - 11 x In
Magnetic trip tol/-20%
MSX
8
COMPACT MCCB WITH THERMAL AND MAGNETIC PROTECTION
MSX 160c - MSX 250c
Technical Information