TECHNICAL DATA
69
Communication
KNX/EIB Bus
Power Supply
By KNX/EIB Bus, 29 V dc SELV
+ 2 1.5 V AAA Alkaline batteries to update date
and time when there is a bus power failure
Bus current consumption
5mA
Bus cable
KNX/EIB TP1
Control elements
1 mini physical address programming key,
10 command and configuration buttons
Display elements
1 LED backlit LCD display (timed to user
intervention),
1 red physical address programming LED
Temperature display range
0 ÷ +45 °C
Reading elements
1 NTC sensor
read resolution: 0.1 °C
read accuracy: ± 0.5 °C to 20 °C
intervals between the next readings: 1 minute
Temperature regulation ranges
T
FROSTPROTECT
.: +2 ÷ +7 °C
T
HIGH TEMPERATURE PROTECTION
+30 ÷ +40 °C
Other set points: +5 ÷ +40 °C
Ambit of use
Indoors, dry places
Operating temperature
-5 ÷ +45 °C
Storage temperature
-25 ÷ +70 °C
Relative humidity
Max 93% (no condensation)
Bus connection
Slot in terminal, 2 pin Ø 1 mm
Protection rating
IP20
Size (L x H x W)
130 x 92 x 23 mm
Reference standards
Low Voltage Standard 2006/95/CE
Electromagnetic Compatibility Standard 89/336/CEE
EN50090-2-2, EN60730-1
Certifications
KNX/EIB
E
N
G
L
I
S
H