Oil and Turbidity Detector TURBISCOPE

OR 52/5

OR 52/6

Important Notes

Electrical connection

To connect the light emitter/receiver, please use a screened, 

multi-core control cable with a min. conductor size of 0.5 

mm². For the light emitter e.g.  2 x 0.5 mm

and for the 

receiver e.g. 4 x 0.5 mm

2

.

Connect the screen in the measuring transducer only once.
Max. line length between light emitter/receiver and measuring 

transducer 50 m.
To use alarm contact 1 for an initial alarm and alarm contact 

2 for the main alarm, for instance, set two different limit 

values.
For condensate monitoring, alarm contact 1 can then be 

used to control a three-way valve, which will discharge 

the unusable condensate if the level of turbidity is too high 

(alarm caused by ingress of oil or start-up protection). Alarm 

contact 2 will then trigger the main alarm.
Note that alarm contacts 1 and 2 and the three-way switch-

over valve will not be switched over in the event of a mal-

function. 
However, the malfunction can be included in the control 

of the three-way switch-over valve as shown in the wiring 

diagram 

Fig. 6

Pneumatic valves can be actuated via solenoid valves.
Valves with a single-phase AC motor and max. power rating 

of 50 VA (see wiring diagram 

Fig.5

 or 

Fig. 6

) can also be 

connected directly. Install a reversing contact in between in 
the case of three-phase actuators. 

Order & Enquiry Specification

GESTRA Oil and Turbidity Detector TURBISCOPE, consisting 
of a measuring sensor with accessories and a measuring 
transducer.

  GESTRA Oil and Turbidity Detector OR 52/5, consisting of 

a measuring sensor ORG 12 (grey cast iron GG-25) and 
a measuring transducer ORT 6.

  GESTRA Oil and Turbidity Detector OR 52/6, consisting 

of a measuring sensor ORG 22 (stainless steel) and a 
measuring transducer ORT 6.

Supply voltage ................................. V (230 V or 115 V).

Ancillaries

Three-way valve, 
Pneumatic actuator, series 500 or 
Three-way solenoid valve.  
Electric actuator, series  200 
Shut-off valve GAV 
Non-return valve RK 86, 20 mbar opening pressure

Valve OPEN: 

Fluid flows through
Valve CLOSED:  

 

Fluid is discharged or 

retained

Wiring diagram 

Switch-over in the event of an alarm

Safety position

Spring to close

Wiring diagram 

Switch-over in the event of an alarm or 

malfunction

Malfunction

Alarm 2  Alarm 1

N

4 - 20 mA
R ≤ 500 

Measuring sensor 

ORG...

Measuring sensor 

ORG...

Measuring transducer 
ORT 6

Measuring transducer 
ORT 6

Disconnecting 

switch
Earthing screw in 

housing

N

L

4 - 20 mA
R ≤ 500 

Alarm 2  Alarm 1

Malfunction

Disconnecting 

switch
Earthing screw in 

housing

N

N

N

L

Safety position

Spring to close

Fig. 5

Fig. 6

Valve OPEN: 

Fluid flows through
Valve CLOSED:  

 

Fluid is discharged or 

retained

GESTRA AG 

Münchener Straße 77, 28215 Bremen, Germany

Telefon  +49 421 3503-0, T49 421 3503-393

E-mail [email protected], Web www.gestra.de

Содержание TURBISCOPE OR 52/5

Страница 1: ...ucer is the operating and display unit for actuating the measuring sensor and analysing the sig nals It visually displays the measurement results and is used to set the measuring equipment It displays the actual value the triggering of ALARM 1 and ALARM 2 limit alarms and malfunctions in the measuring sensor Limit values are set and displayed on the measuring transducer Directives and Standards Vd...

Страница 2: ...ional Power consumption 25 VA Fuse Thermal fuse M 0 2 A 5 x 20 at 230 V Thermal fuse M 0 4 A 5 x 20 at 115 V Thermal fuse M 1 0 A 5 x 20 at 24 V Housing Field case for wall mounting Housing material Die cast aluminium Protection IP 65 to EN 60529 Admissible ambient temperature 0 C 55 C Weight approx 3 6 kg Oil and Turbidity Detector TURBISCOPE OR 52 5 OR 52 6 Dimensions ALARM 1 2 ppm sec cal 0 OIL...

Страница 3: ...r ORT 6 Measuring sensor ORG 12 ORG 22 Fig 4 Important Notes Condensate monitoring Installation In steam boilers and hot water plants the oil and turbid ity detector can monitor water condensate and feedwater systems for the ingress of oil and grease EN 12952 7 EN 12953 6 TRD 604 sheet 1 Fig 4 shows a typical arrangement of the monitoring equipment with flow from left to right If there is an ingre...

Страница 4: ...es with a single phase AC motor and max power rating of 50 VA see wiring diagram Fig 5 or Fig 6 can also be connected directly Install a reversing contact in between in the case of three phase actuators Order Enquiry Specification GESTRA Oil and Turbidity Detector TURBISCOPE consisting of a measuring sensor with accessories and a measuring transducer GESTRA Oil andTurbidity Detector OR 52 5 consis...

Отзывы: