Operation Malfunctions
Fault-finding list for troubleshooting
Normal operation – Temperature switch triggers an alarm
Fault:
The temperature switch triggers an alarm during normal operation.
Remedy:
Make sure that the green LED is illuminated. If this is not the case check whether the equip-
ment is supplied with mains voltage.
Remedy:
Check whether the cable leading to the resistance thermometer is damaged.
Remedy:
Check whether the resistance thermometer gives correct readings
(basic values of measuring resistor to DIN EN 6075 for Pt 00).
Danger
The terminal strip of the equipment is live during operation.
This presents the risk of severe cases of electric shock!
Cut off power supply before mounting or removing the terminal strips and the housing
cover.
If faults occur that are not listed above or cannot be corrected, please contact our service centre or
authorized agency in your country.