6
TRS 5-40
DIN registration number
TR / TW 118206
Input / output
Interface for CAN bus to ISO 11898 CANopen
with power supply 18 – 36 V DC, short-circuit protected
Outputs
4 volt-free relay contacts
Contact material AgNi 0.15
Max. contact rating with switching voltages 24 V AC/DC, 115 V AC and 230 V AC:
Resistive / inductive 4 A.
Contactors must be provided with interference suppressors (RC combinations) as specified by the
manufacturer.
2 Analog outputs 4 – 20 mA, load 500 Ω for actual value indication (optional)
Channel 1: e.g. inlet temperature
Channel 2: e.g. return temperature
Switching hysteresis
for MAX switchpoints –2 °C,
for MIN switch 2 °C
Indicators and adjustors
2 test buttons for checking relays,
4 LEDs for alarm and error messages,
1 LED Power,
1 LED Bus status,
1 10-pole code switch for setting the node ID, the baud rate and the system configuration
Mains voltage
230 V +10 / –15 %, 50 – 60 Hz
115 V +10 / –15 %, 50 – 60 Hz (optional)
24 V +10 / –15 %, 50 – 60 Hz (optional)
Power consumption
10 VA
Protection
Housing: IP 40 to EN 60529
Terminal strip: IP 20 to EN 60529
Admissible ambient temperature
0 – 55 °C
Housing
Housing material: Base: polycarbonate, black; Front panel: polycarbonat, grey
Conductor size: 1 x 4.0 mm
2
solid per wire or
1 x 2.5 mm
2
per stranded wire with sleeve to DIN 46228 or
2 x 1.4 mm
2
per stranded wire with sleeve to DIN 46228; terminal strips can be detached
Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715
Weight
approx. 0.8 kg
Technical Data