System Malfunctions
– continued –
The four indicator LEDs flash slowly.
High/low-level alarm
Fault:
The max. admissible temperature in the electrode terminal box is exceeded.
Remedy:
Insulate electrode flange to protect the equipment against heat radiation.
The four indicator LEDs flash rapidly.
High/low-level alarm
As soon as the temperature drops below the max. admissible limit the equipment automatically returns
to normal operation.
Fault:
The CAN bus line between the nodes is interrupted.
Remedy:
Check wiring and terminals. Restart system
Fault:
Incorrect node ID(s).
Remedy:
Set correct nodes ID(s), referring to section “Basic Adjustments” or “Annex”.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.