42
NRGT 26-2n - Installation & Operating Manual -
850879-00
Starting, operation and testing
If password protection is enabled, you must enter the password before you can initiate
the test function.
Test
Checking function via simulation in operating mode
In operating mode:
Press the rotary knob on the
NRGT 26-2n and hold until the
end of the test:
On each test, the equipment
function toggles between
levels 0% and 100%, and the
actual value output delivers the
corresponding signal, 4 mA or
20 mA.
Display:
0000 (%) or 0100 (%)
The test simulates water falling below the
LW mark or rising above the HW mark.
The simulated reading is displayed
for each test.
LED 2
:
Operating LED lights up green
Test function is active
LED 1:
Fault LED is OFF
No fault
■
The current output can be simulated and tested
■
When the rotary knob is released, the test ends
Faulty equipment is a risk to system availability.
■
If the level transmitter does not behave as described above, the equipment may be faulty.
■
Perform failure analysis.
■
The NRGT 26-2n level transmitter may only be repaired by the manufacturer, GESTRA AG.
■
Only replace faulty equipment with identical equipment from GESTRA AG.