Action against high-frequency interference
High-frequency interference can be caused by out-of-phase switching operations. If such in-
terference occurs and results in sporadic failure, we recommend taking the following action to
suppress interference:
■
Provide inductive loads with RC combinations as specified by the manufacturer.
■
Route the connecting cables to the conductivity electrode separately from power lines.
■
Increase the distance from sources of interference.
■
Check that the shield is correctly connected. Check the shield of items of equipment with the
aid of the Installation & Operating Manuals. If equalizing currents are likely (outdoor installa-
tions), connect the shield on one side only.
■
Suppress HF interference using hinged-shell ferrite rings.