14
Operating the conductivity switch
Key to codes on seven-segment display
Code
Description
Indicated when rotary button is turned to the right:
AL.Hi
Alarm High
MAX switchpoint
adjustable between 1 and 9999 μS/cm
AL.Lo
Alarm Low
MIN switchpoint
CF
Correction Factor
Correction factor, adjustable between 0.05 and 5,000, adjustable
in increments of 0.001
inP
Input Pt 100
Temperature compensation YES (no)
tC
Temperature coefficient Temperature coefficient T
k
0.0 – 3.0 % per °C,
adjustable in increments of 1 %.
tESt
Test
Tests output relays
Indicated when in parameterization mode:
quit
Quit
Input not confirmed
done
Done
Input confirmed
Indicated if malfunctions occur:
E.001
Error
Temperature sensor defective, temperature reading too low
E.002
Error
Temperature sensor defective, temperature reading too high
E.005
Error
Sensor defective, measured value too low
E.006
Error
Sensor defective, measured value too high
E.013
Error
MIN switchpoint above MAX switchpoint
Fig. 5
MAX LED
red
MIN LED
red
Seven-segment
display
Rotary button with
integrated push-
button
5432