Configuring the conductivity controller
Setting correction factor C
1.
Establish a
reference reading
.
Once service temperature is reached,
measure the conductivity of a sample of
water.
2.
Tap the
“
Correction factor C
” input
field.
3.
Either type in the correction factor “
C
”
or
Enter the
reference reading
“
X
Ref
” you
previously measured.
Display after entering
reference reading “X
Ref
”
Confirm the calculated correction
factor “
C
”.
Reject the calculated correction
factor “
C
”.
Display when limit is exceeded
If correction factor “
C
” exceeds the
limit 5 1/cm, a warning appears.
In this case, you have no choice but to reject
the calculated correction factor “
C
”.
A value > 5 1/cm indicates heavy
soiling of the conductivity electrode.
The conductivity electrode must be
cleaned.