Attention
Before carrying out the fault diagnosis please check:
Supply voltage:
Is the equipment supplied with the mains voltage specified on the name plate?
Wiring:
Is the wiring in accordance with the wiring diagram?
Troubleshooting
Indication, diagnosis and remedy
Attention
n
Please refer to the installation operating manuals for LRG 12-2, LRG 16-4, LRG 16-9,
LRG 17-1, LRG 19-1, TRG 5-.. and LRGT 1.-.. for further fault-finding and trouble-
shooting.
Note
If a malfunction occurs in the conductivity controller, a MAX alarm will be triggered and the
equipment is restarted. Should this happen over and over again, replace the equipment
with a new one.
Faults indicated by the seven-segment display
Error code
Error
Remedy
E.001
Temperature sensor defective, temperature
reading too low
Check resistance thermometer, conductivity electrode
LRG 16-9 and, if necessary, replace it with a new one.
Check wiring (short circuit, interruption?)
E.002
Temperature sensor defective, temperature
reading too high
E.005
Conductivity electrode defective, measured
value too low
Check conductivity electrode and, if necessary, replace
it. Check electrical connection.
Conductivity transmitter defective,
measuring current < 4 mA
Check conductivity transmitter and, if necessary,
replace it. Check electrical connection.
E.006
Conductivity electrode defective, measured
value too high
Check conductivity electrode and, if necessary, replace
it. Check electrical connection. Check boiler water.
Conductivity transmitter defective,
measuring current > 20 mA
Check conductivity transmitter and, if necessary,
replace it. Check electrical connection.
In the event of a malfunction a MAX alarm will be raised and the continuous blowdown valve is motored
into the OPERATING position.
Malfunction without indication
Error
Remedy
Actual value < setpoint.
The continuous blowdown valve opens.
Check code switch S4. The switch must be set to ON.