Functions 

Functions 

a. 

When the PTC heater detector SENSOR sensing the temperature gets to 70

, the PTC heater will 

Force OFF. Ventilation fan and the circulation fan will run by the original setting;

b. 

When  the  PTC  heater  detector  SENSOR  induction  temperature  gets  to  70

  ~  75

, If the 

temperature detector SENSOR detected temperature dropped below 50

, PTC will recover and 

turn on automatically , the fan gear set will back to the previous state; (Between 70

 ~ 75

, the 

machine does not display the fault code “HE”, buzzer will not respond).

c.  When the temperature rising to 75

, the PTC heater will Force OFF, ventilation fan will shift to 

high speed, display board shows high temperature protection fault code “HE”, buzzer will ring once 

every second.

a.  During the high temperature protection fault, if temperature cannot dropped to below 55

 , the 

ventilation  Fan  continues  to  run  in  high  speed  gear,  and  any  changing  in  function  mode  is  not 

allowed. User can only turn off the machine manually. After turning off manually, the fault code will 

be erased. 

b.  If the temperature dropped below 55

, PTC will recover and be turned on automatically , the fan 

gear set will back to the previous state; 

 

 

 

 

 

 

      

Failure of Temperature Sensor 

1. 

The  Environment  Temperature  Sensor  continuously  test  for  5  seconds  for  fault  condition,  the 

display board shows Fault Code “

2.  The PTC Temperature Sensor continuously test for 5 seconds for fault condition, the display board 

shows Fault Code “

3. 

To test Both Environment Temperature Sensor and PTC Temperature Sensor faults, all overload are 

closed, the display board shows Fault Code (If there are a few faults happened at the same time, 

Fault Code “

” and “

”will be displayed alternatively for 3 seconds) and the machine is Force 

Stop. Any changing in function mode is not allowed, until after the Temperature Sensor Fault is 

eliminated before the machine can function again. 

 

 

 

Fault Code

1.  High Temperature Protection: display board shows Fault Code, “

2. 

Environmental Thermal Package Failure: display board shows Fault Code “

3.  PTC Thermal Package Failure: display board shows fault code “

”  

 

Safe Protection of Temperature Sensor

 

• 

Temperature  sensor  protection  is  only  applicable  to  the  functions  of:  “Auto  Function

 

 

”,            

“Warm Function

 

 ”, “Preheat

   

”, and “Dry Function

   

• 

When the room temperature detection SENSOR sensing the temperature gets to 50

, the PTC  

heater will be Force OFF. Ventilation fan and the circulation fan will run by the original setting;

• 

When the room temperature detection SENSOR sensing the temperature gets to 50

 ~ 55

, and 

the temperature has not dropped, the PTC heater is kept OFF, ventilation fan and the circulation fan 

will run by the original setting; (Between 50

 ~ 55

, the machine does not display the fault code 

“HE”, buzzer will not respond).

• 

If room temperature detector SENSOR dropped below 40

, PTC will recover and be turned on 

automatically , the fan gear will be set back to the previous state; 

• 

When the temperature rising to 55

, the PTC heater will Force OFF, ventilation fan will shift to high 

speed, display board shows high temperature protection fault code “

”, buzzer will ring once 

every second.

• 

During the high temperature protection fault, if temperature cannot dropped to below 40

, the 

ventilation  Fan  continues  to  run  in  high  speed  gear,  and  any  changing  in  function  mode  is  not 

allowed. User can only turn off the machine manually. After turning off manually, the fault code will 

be erased. 

• 

If the temperature is detected to have dropped below 40

, PTC will recover and be turned on 

automatically , the fan gear set will back to the previous state;

Automatic Function   

• 

Press “AUTO  ” button, the “AUTO 

” indication light gets on, and the machine starts to run in 

automatic mode, and the air volume runs at the mode of “Low SPEED  ”. After 20 seconds, the 

machine will run at different modes according to the current room temperature.

In the process of the machine running, from other models for automatic switching function, with 

display board “AUTO 

” indication light got on, automatic functions directly start to work, without 

waiting for running at low speed for 20 seconds first, and the machine automatically selects run 

mode according to the current room temperature. See below for more information on automatic 

setting selection criteria. 

The automatic setting follows this order:

1.  Room temperature > 24 degrees is tested for 10 seconds, automatically turns on the 

“AUTO  ”mode, runs in “High SPEED 

” , it is not changeable.

2.  Room temperature < 20 degrees is tested for 10 seconds, automatically turns on the 

“WARM  ” mode, starts the PTC electric heater, runs in “High SPEED 

”, it is not 

changeable.

3.  20 degrees < room temperature < 24 degrees is tested for 10 seconds, automatically 

turns on the “DRY 

” mode, starts the PTC electric heater, runs in “High SPEED 

”, it is 

not changeable.

4. 

After running for 1.5 hours, it will turn to  

 mode. This is to cool down the PTC heater. It 

will last for 30 minutes, runs in “High SPEED 

”, it is not changeable. 

• 

Timer: Default setting is 2 hours, it is not changeable. Time displayed is on the basis of the 

remaining run time.

• 

Stop: Press the “STOP 

” button or when pre-set time is over, LED indication light gets off, the 

remaining time display will also be off, and the machine stops automatically. When running in 

the heat or dry mode, press “STOP  ” after shutdown, fans will still be running for about 25 

seconds, in order to cool down the PTC heater.

Содержание HTB-148

Страница 1: ...Please read these instructions and warranty information carefully before use and keep them handy for future reference Online Warranty Registration HTB 148 Multi Purpose Bathroom Heater U S E R M A N U...

Страница 2: ...tructure 06 Installation 08 Functions 09 Cleaning Maintenance 14 Troubleshooting 15 Technical Specifications 15 Warranty Terms Conditions 27 Please register your warranty information now For Warranty...

Страница 3: ...d be sure to have it replaced by the manufacturer or their agent Failure to follow this advice may result in death NOTICE On product safety and the safety of users must strictly operate according to t...

Страница 4: ...165 55 35 225 19 255 205 97 99 53 33 5 8 8 Product Structure Product Structure Wireless Remote Control FRONT BOTTOM REMOTE CONTROL SIDE Main Body Product Dimension Air Filter Main Body Receiver Air Lo...

Страница 5: ...n Functions Installation Instruction of Remote Control Button Window Type Installation Front cover size 254mm 254mm Window frame size 215mm 209mm Window type installation must be transverse installati...

Страница 6: ...e time duration by pressing the or of the TIMER button the time can be set form 1 hour to 24 hours The remaining time will be showed on the LED display The time selection will be recorded in memory wh...

Страница 7: ...ter is kept OFF ventilation fan and the circulation fan will run by the original setting Between 50 55 the machine does not display the fault code HE buzzer will not respond If room temperature detect...

Страница 8: ...and put it in water to clean the dust and dirty after around 1 months usually then put it back to the cover after the filter dry Safety Do not put your hands into the machine when running to avoid in...

Страница 9: ...P 17 P 16 17 19 21 22 25 25 26 27 3 3 8 5 3mm 250V 13A...

Страница 10: ...P 19 P 18 2 3m 2 240mm h 8...

Страница 11: ...P 21 P 20 ST3 9 25 7 ST4 2 25 7 6 28 2 4 2 254mm X 254mm 219mm X 209mm 1 2 3 2 3 47 4 216 234 255 213 23 165 55 35 225 19 255 205 97 99 53 33 5 8 8...

Страница 12: ...P 23 P 22 2 1 24 LED 25 PTC 2 1 24 24 24 24 24 24 24 24 24 4 1 24 PTC 25 PTC 2 1 24 4 1 24 60 90 90 15 24...

Страница 13: ...0 20s 1 10s 24 2 10s 20 PTC 3 10s 20 24 PTC 4 1 5 30 PTC 2 2 25 PTC PTC 50 PTC 50 55 PTC 40 PTC 50 55 55 PTC 40 40 PTC PTC 80 PTC PTC 80 90 PTC 65 PTC 80 90 90 PTC OFF 65 65 PTC 1 5 2 PTC 5 PTC 3 PTC...

Страница 14: ...defective part 5 This warranty will be void if there is any transfer of ownership from the original purchaser 1 2 3 4 5 Serial No Purchased From Invoice No Purchase Date Model No Please fill out the...

Страница 15: ...980 8308 Fax 86 757 2980 8318 8th Xinxiang Road Wusha Industrial Park Daliang Shunde Foshan Guangdong 3 F Edificio Industrial Pou Fung 145 Rua de Francisco Xavier Pereira Macau Tel 853 2875 2699 Fax 8...

Отзывы: