3. Montage and Wiring

• Please read instructions and markings before montage.
• Mount the device on the wall and screw from montage holes to
fix. 
• Make sure device is not energized before making connections.
• Check cable current carrying capacity for maximum
requirements. 

4. Usage

4.1.  Turn On and Off

Device may turn on after proper montage and wiring. 

To turn on, follow these steps: 

1.

Switch AC MCB position to ON

2.

Switch DC MCB position to ON

To turn off, follow these steps: 

1.

Switch DC MCB position to OFF

2.

Switch AC MCB position to OFF

4.2.  Control Unit and Settings 

GEPA ARG-

24L Series Battery Charger & Battery Group’s control unit, BCC-2 

Control Unit, provides human machine interface. 
Output voltage and current is adjustable; output voltage and current live 
measurements and alarm indicators are available through control unit. 

To adjust settings parameters follow steps at the below: 

1.

Press

 button. 

2.

Voltage display blinks. It displays adjusted voltage output value. Press up or
down buttons to adjust. 

3.

Press

 button again to save new parameter. 

4.

Current display blinks. It displays adjusted float current output limit value.
Press up or down buttons to adjust. 

5.

Press

 button again to save new parameter. 

In case of high current demand 

–like deep discharged battery group or any device requires high current– output voltage 

might be lower than adjusted.  

Device can display battery group voltage without AC supply voltage. Press 

Test

 button to make the device to display battery group 

voltage while AC supply voltage not applied. 

4.3.  Alarm Function 

Device has an alarm contact output. NO alarm contact trips in case of: 

High(240 V

AC

) or low(190 V

AC

) AC supply voltage

High(30 V

DC

)  or low(20 V

DC

) DC output voltage

Leakage between DC output and earth

Output current is higher than adjusted output current value