3.6.4  Connecting Backup Battery 

GV-AS Power Board supports any battery of 12V 5Ah to provide battery backup when the 
mains supply fails. When the battery is connected, the Power and Charging LEDs will light. 
When the mains supply is removed and the battery voltage level is above 10.2V, the 
Discharging LED will light and the battery will support normal operation.   
 
 

 

Figure 3-37 

 

Note:

 An internal battery verification will cut the battery power if the battery voltage level falls 

below 10.2V.  

 

Содержание GV-AS Series

Страница 1: ...GV AS Controller Before attempting to connect or operate this product please read these instructions carefully and save this manual for future use Installation Guide...

Страница 2: ...or omissions No liability is assumed for incidental or consequential damages arising from the use of the information or products contained herein Features and specifications are subject to change with...

Страница 3: ...etwork Connection 9 1 2 4 C Switches 9 1 2 5 Connecting the Power 10 1 2 6 Fitting the Battery 10 1 3 Programming Mode 11 1 3 1 Quick Reference of Programming Table 13 1 3 2 Accessing the Card Manager...

Страница 4: ...eeper 36 2 6 GV AS110 Specifications 38 3 GV AS400 Controller 39 3 1 Introduction 40 3 1 1 Main Features 40 3 1 2 Packing List 40 3 2 Installation 42 3 2 1 Connecting Card Readers 42 3 2 1 A Wiegand R...

Страница 5: ...Main Features 77 3 6 2 Connecting Output Devices 78 3 6 3 Connecting the Power 79 3 6 4 Connecting Backup Battery 80 3 7 GV AS400 Specifications 81 4 Optional Devices 82 4 1 Optional GV ASBox 83 4 1...

Страница 6: ...sed Configurations of GV AS100 GV AS110 128 4 2 5 A Basic Setting 128 4 2 5 B Advanced Settings 129 4 2 6 GV ASNet Specifications 139 5 GV ASManager Quick Start Guide 140 5 1 Introduction 141 5 2 Inst...

Страница 7: ...he battery is an uninterruptible power supply UPS device designed to continuously supply GV AS Controllers power during power failure GV Reader The reader has both Wiegand and RS 485 outputs that can...

Страница 8: ...x 17 5 x 4 4 in and 300 W x 420 H x 86 D mm 11 8 x 16 5 x 3 4 in Push Button Switch The push button switch can be integrated with access control system allowing door exit by momentarily activating or...

Страница 9: ...reader for entry and some doors are equipped with two card readers for entry and exit For example a building includes both office and laboratory applications One way traffic Two doors are applied for...

Страница 10: ......

Страница 11: ...1 GV AS100 Controller...

Страница 12: ...dalone unit the programming is either done on the keypad or from the software GV ASManager through the RS 485 connection GV AS100 is suitable not only for any normal door control but also for parking...

Страница 13: ...485 mode Easy programming from keypad Anti Passback APB support Built in 3 digital inputs and 2 relay outputs 1 Wiegand output 26 64 bits for extra reader programming 1 door expandable to 2 doors wit...

Страница 14: ...4 1 1 3 GV AS100 Board Layout Figure 1 3...

Страница 15: ...Pin Function Pin Function 1 12V Power 9 12V Power Supply 17 Door COM 2 GND 10 GND 18 Door NC 3 RS 485 A for ASBox ASNet or PC connection 11 Sensor IN1 19 Door NO 4 RS 485 A for ASBox ASNet or PC conne...

Страница 16: ...or wiring Pin Function 7 Wiegand Data 0 8 Wiegand Data 1 9 12V Power Supply 10 GND 1 2 2 Connecting Input Devices GV AS100 supports 3 types of inputs 1 Sensor inputs e g door status sensor 2 Button in...

Страница 17: ...0V AC 30V DC Continuous Load Current 5A NO 3A NC Note Absolute Maximum Ratings are those values beyond which damage to GV AS100 circuit board may occur Continuous operation of GV AS100 at the absolute...

Страница 18: ...required IMPORTANT To enable connecting to PC Switch 1 must be turned on See 1 2 4 C Switches 1 2 4 A RS 485 Connection The figure below illustrates the RS 485 connection to the computer For this conn...

Страница 19: ...d connectors on GV AS100 Pin Function Pin Function 1 Power In 12V 3 RS 485 A 2 GND 4 RS 485 A Also see 4 1 4 A Connecting GV AS100 GV AS110 1 2 4 C Switches Switch 1 When Switch 1 is ON GV AS100 can c...

Страница 20: ...pplied to the unit when all connections are completed and tested 1 2 6 Fitting the Battery GV AS100 includes a 3V lithium battery providing power to database and real time clock circuitry When the pow...

Страница 21: ...you can press any four digits on the keypad to change the default value The double confirmation of the new PIN code is required After this the LCD should display the message of success After the Maste...

Страница 22: ...S100 you also need to know the following keys Key Function Used to cancel the selection or go back to the previous page Used to save the data that was modified or programmed in the system and quit 0 U...

Страница 23: ...xed Card Mode Fixed Card PIN Fixed Card Common Local Unlock Mode Local Lock Mode AS100 Function GV ASBox Control Type Door Entry Type Anti Passback Door Exit Type Anti Passback Parking Entry Type Anti...

Страница 24: ...d New Card 3 Press The LCD displays Enter New Card 4 To add a card you can either press the card number or present the card to the unit The LCD displays the card number and these options 1 N 2 A 3 B 4...

Страница 25: ...ards can be granted access and no one can program the unit Only the security card that is associated with a PIN code can be used to disarm the unit 1 3 3 A Enabling the Security Mode Before you can ac...

Страница 26: ...55 Set Auth Mode Sets an authentication mode for the door gate Auth Schedule Follows the authentication schedule set on GV ASManager Fixed Card Mode Grants access after the card is presented Ignores t...

Страница 27: ...Anti Passback function Master PIN Change Changes the PIN code of the Master Card Local Rest Time Sets the time 1 to 255 sec that a door gate remains open after which the door will automatically be loc...

Страница 28: ...V ASNet failed Comm Normal The connection to GV ASBox GV ASNet succeeded Memory s State Displays the memory usage of GV AS100 Capacity Displays the total number of events that can be recorded on GV AS...

Страница 29: ...ack the unit to factory defaults IMPORTANT Restoring default settings will delete all cards enrolled on GV AS100 1 Press the code 737 RES 2 Present the Master Card and enter PIN Code The LCD displays...

Страница 30: ...AS100 can communicate with GV ASManager over the network Using GV ASBox or GV ASNet you can also access the Web interface of GV AS100 Refer to Chapter 4 Optional Devices to see how to connect a GV AS...

Страница 31: ...100 240V AC 50 60Hz 1 Wiegand interface 26 64 bit format Wiegand Interface 12V DC Power Supply 200mA Communication Protocol RS 485 Input 3 inputs dry contact NO NC Digital I O Output 2 outputs Operati...

Страница 32: ...2 GV AS110 Controller...

Страница 33: ...ng used as a standalone unit the programming is either done on the keypad or from the software GV ASManager through the RS 485 connection GV AS110 is suitable not only for any normal door control but...

Страница 34: ...ogramming from keypad Anti Passback APB support Built in 3 digital inputs and 2 relay outputs 1 Wiegand output 26 64 bits for extra reader programming 1 door expandable to 2 doors with optional GV ASB...

Страница 35: ...ront View Rear View Figure 2 3 Wire color Definition Red 12V Black GND Green Wiegand Data 0 White Wiegand Date 1 Blue RS485 Light Blue RS485 Yellow Door Sensor IN1 Orange Button IN2 Pink Fire Sensor I...

Страница 36: ...source to power the Wiegand reader 2 2 2 Connecting Input Devices GV AS110 supports 3 types of inputs 1 Sensor inputs e g door status sensor 2 Button inputs e g door opener 3 Fire Sensor inputs e g fi...

Страница 37: ...0V AC 220V DC Continuous Load Current 1A 30V DC 0 3A 125V AC Note Absolute Maximum Ratings are those values beyond which damage to GV AS110 circuit board may occur Continuous operation of GV AS110 at...

Страница 38: ...For network connection an optional GV ASBox or GV ASNet is required 2 2 4 A RS 485 Connection The figure below illustrates the RS 485 connection to the computer For this connection a RS 485 to RS 232...

Страница 39: ...AS110 or 4 2 4A Connecting GV AS100 GV AS110 to see how to connect to GV ASBox or GV ASNet 2 2 5 Connecting the Power The supplied AC adaptor can be connected to any power source supplying from 100 to...

Страница 40: ...reate the Master Cards 1 Power on the unit The LED flashes blue 2 Present a card to be the Enroll Card 3 Present a card to be the Delete Card 4 The GV AS110 will automatically load default and the LED...

Страница 41: ...erson B card is also presented together 2 Two person B Card In the Two Person Entrance Exit mode the door unlocks only when two person A card is also presented together 3 Security Card The Security Ca...

Страница 42: ...78_ _ _ 1 255 seconds Sets a time that the door gate will remain open after which the door will automatically be locked For example to set the lock reset time to be 120 seconds press 578120 Held Open...

Страница 43: ...te Elevator Type GV AS100 reader is installed in the elevator for access control For example to set the GV AS110 as an exit reader of a door press 3432 Set Authentication Mode 526_ Schedule Mode 0 Fix...

Страница 44: ...o Person Entrance 873_ Disable 0 Enable 1 When Two Person Entrance mode is enabled both Two Person A Card and Two Person B Card must be presented to unlock the entrance To enable Two Person Entrance p...

Страница 45: ...GV ASNet GV AS110 can communicate with GV ASManager over the network Using GV ASBox or GV ASNet you can also access the Web interface of GV AS110 Refer to Chapter 4 Optional Devices to see how to conn...

Страница 46: ...nt Security Mode enabled Yellow One long beep Security Mode disabled Returns to the LED status of the previous mode One long beep Tamper Forced Open Alarm Flashes green and red Constant beep until ala...

Страница 47: ...GV AS110 Controller 37 2 Firmware update Flashes red green and blue Silent Firmware update failed Flashes purple Constant beep Factory default Flashes blue Silent...

Страница 48: ...100 240V AC 50 60Hz 1 Wiegand interface 26 64 bit format Wiegand Interface 12V DC Power Supply 200mA Communication Protocol RS 485 Input 3 inputs dry contact NO NC Digital I O Output 2 outputs Operati...

Страница 49: ...3 GV AS400 Controller...

Страница 50: ...ders and GV GF Fingerprint Readers Built in 16 digital inputs and 16 relay outputs I O capability expandable to 64 digital inputs and 64 relay outputs with GV IO Box connected Suitable for door parkin...

Страница 51: ...0 Board Layout 1 2 3 4 5 6 7 8 ON EGE 1 2 3 4 5 6 7 8 ON EGE RS 485 NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM NO NC COM Wiegand A Wiegand B Wiegand C Wiegand D Wiegand E Wi...

Страница 52: ...Connecting Card Readers GV AS400 supports two types of card reader interfaces Wiegand and RS 485 The Wiegand interface is compatible with any Wiegand card readers of 26 to 64 bits The RS 485 interface...

Страница 53: ...ssignments of Wiegand inputs on GV AS400 Please consult the documentation of your Wiegand reader for wiring Pin Function GND GND of the Power Supply D0 Wiegand Data 0 D1 Wiegand Data 1 12V 12V Power S...

Страница 54: ...ingle RS 485 cable to the RS 485 interface on GV AS400 When multiple readers are connected together an extra power supply to each unit is required Use 12V power output and GND on the Wiegand connector...

Страница 55: ...shown below to change the input state for NO or NC When the switch is pushed up the state is NC When the switch is pushed down the state is NO SW2 is used for inputs 1 to 8 and SW3 is for inputs 9 to...

Страница 56: ...cation that the output device is activated Besides having the on board capability of monitoring 16 outputs GV AS400 can be expanded to 64 outputs if 4 units of GV IO Boxes 16 Ports are connected For d...

Страница 57: ...y accept the power from GV AS400 circuit board Check if your output device meets the following absolute maximum ratings before connecting it to any of outputs 9 16 Breakdown Voltage 350V DC AC Continu...

Страница 58: ...s 9 16 The following figure and table shows how to connect the beeper wire of GV Reader to GV AS400 GND RS485 RS485 12V GND D0 D1 12V OUT09 Figure 3 7 Electric Wires on GV Reader Output on GV AS400 Ye...

Страница 59: ...e GV AS400 stores this information on the database for later transmission 3 2 5 Connecting the Power The supplied AC adaptor can be connected to any power source supplying from 100 to 250V Using the s...

Страница 60: ...16 ports of inputs and outputs respectively Connect GV IO Box to the RS 485 connectors as illustrated below Multiple GV IO Boxes of different port types can be connected on a single RS 485 cable to w...

Страница 61: ...oviding power to database and real time clock circuitry When the power in the battery becomes low the message Low Battery will appear on GV ASKeypad In this case please replace the battery The databas...

Страница 62: ...is set to the right position Advanced Settings are not accessible For details on Advanced Settings see 3 4 Web Based Configurations Figure 3 12 3 3 2 Resetting the GV AS400 1 To reset GV AS400 press...

Страница 63: ...y take up to 3 minutes to restore Basic Settings of GV AS400 to default factory values Figure 3 14 To restore All Settings to factory defaults 1 Remove the jumper cap from JP6 to JP7 2 Press the Reset...

Страница 64: ...Jumper and plug it into JP7 or plug GV ASKeypad to GV AS400 Figure 3 16 2 On the Web interface of GV AS400 Controller click Firmware Update from the left menu This dialog box appears Figure 3 17 3 Cli...

Страница 65: ...complete the following dialog box appears Figure 3 18 6 Click OK The GV AS400 Controller will restart automatically Note It is required to restart GV AS400 Controller after firmware upgrade Without r...

Страница 66: ...tps 192 168 0 100 The default Username and Password for login are admin Note the computer used to set the IP address must be at the same network or subnet sequence assigned to GV AS400 3 GV AS400 is a...

Страница 67: ...device time and edit the input output functions The changes in some of the Advanced Settings page will effect the options available on other pages Below is a diagram drawing the relationships between...

Страница 68: ...AS400 ID number can only be between 1 and 255 Door Gate Select the function type and authentication mode for the use of Door Gate A B C and D Function Select the function for the reader connected to...

Страница 69: ...chedule of GV ASManager Authentication Schedule Mode Follows the authentication schedule set on GV ASManager Anti Passback This option lets you set the Anti Passback function across multiple door cont...

Страница 70: ...contents of Parameter Setting change based on your settings for Door Gate in the Function Setting page Figure 3 20 Figure 3 21 IMPORTANT Once connecting to GV AS400 GV ASManager will load its paramet...

Страница 71: ...Locks or unlocks the door when a fire condition occurs Otherwise remains the door s current state by selecting Unchanged Alarm Continuous Time Sets the time 1 to 10 sec that the alarm will continuous...

Страница 72: ...set period of time Forced Open This alarm activates whenever the door is opened by force Fire Alarm This alarm activates whenever fire is detected Access Denied This alarm activates whenever entry is...

Страница 73: ...lected as Authentication Mode in the Function Setting page Figure 3 20 you can gain access by using a card or entering this Common Password door s password Figure 3 22 Click Submit button to save the...

Страница 74: ...Local Time Disable Disable the manual configuration of time and date Setup Enable the manual configuration of Time Zone Date and Time for GV AS400 Daylight Savings Time DST Disable Disable the manual...

Страница 75: ...ibe the sensor input Through the sensor input an alarm event can be detected and the event may also trigger the alarm Figure 3 25 1 Input Type Configure the input type Input Type defines the type of s...

Страница 76: ...e Door Contact sensor detects unauthorized access a Force Open type of event occurs and the event may trigger the Force Open alarm Gate Fire Zone Tamper Zone Exit Button Car Detection See the Door Inp...

Страница 77: ...devices and Exit Button Select from the drop down list to configure the Output Type No 1 Figure 3 27 Depending on the chosen Output Type either Output Function No 2 Figure 3 27 or Output Conditions N...

Страница 78: ...Output Type Output Function Description Electric Lock Output is triggered when the card is presented to open the locking device Event Alarm Output is triggered when the defined alarm events occur Secu...

Страница 79: ...01 08 Gate Gate Open Alarm Output is triggered when the parking gate is open Beeper Green LED Output 09 16 Gate Red LED See the same function above When Relay is selected as Output Type these Output F...

Страница 80: ...certain conditions as AND and certain conditions as OR For Pulse output type the output is triggered for the amount of time set in the Sec field seconds In the Output Condition settings these Output T...

Страница 81: ...ges to its previous state 3 4 3 F Wiegand Function In the left menu click Wiegand Setting This AS400 Wiegand Configuration page appears Use the drop down list to select the location where the Wiegand...

Страница 82: ...eader This AS400 Extended Reader Configuration page appears Figure 3 31 GV Reader Function Define each GV Reader connected to GV AS400 If you are using a GV RK1352 Reader type the serial number found...

Страница 83: ...to detect GV GF Fingerprint Reader If any GV GF Fingerprint Reader is detected a green mark will appear in the Setting Status field 3 4 4 B Extended I O In the left menu click Extended I O This AS400...

Страница 84: ...GV AS400 installed at different locations Features 2 Lines x 16 English Characters 4 x 4 Keys 3 5 1 Installation 1 Flip both clips of the 26 pin connector on GV AS400 2 Using the supplied 26 pin ribbo...

Страница 85: ...l load its parameters to GV AS400 That means some of configurations you have configured may be overwritten by GV ASManager later 1 Press the code 738 2 Press the default PIN code 1234 3 To set paramet...

Страница 86: ...the door gate to be exit or entry For the same function see 3 4 Web Based Configurations 3 5 2 B Displaying System Information To display system information press the code 347 To change options or vie...

Страница 87: ...nly supplies 12V power combining with GV AS Power Board GV AS 400 can directly drive output devices of 24V AC DC and 10V to 13V DC Additionally GV AS Power Board supports the battery backup to ensure...

Страница 88: ...ource is AC but the Vout Swtich is switched to DC Output the two power outputs of 24V DC will be enlarged to 30V DC 10V to 13V DC GV AS Power Board provides six power outputs of 10V to 13V DC in order...

Страница 89: ...device Figure 3 35 3 6 3 Connecting the Power GV AS Power Board accepts the power input of either 24V AC or 24V DC After wiring the power source to the proper connectors on GV AS Power Board turn the...

Страница 90: ...the battery is connected the Power and Charging LEDs will light When the mains supply is removed and the battery voltage level is above 10 2V the Discharging LED will light and the battery will suppo...

Страница 91: ...rs and GV GF Fingerprint Readers max 8 readers 8 Wiegand interfaces 26 64 bit format Wiegand Interface 12V DC power supply 200mA Communication TCP IP Input 16 inputs dry contact NO NC Output 8 relay o...

Страница 92: ...4 Optional Devices...

Страница 93: ...y to GV AS100 GV AS110 Extend GV AS100 GV AS110 from 1 door to 2 door controller Support 1 Wiegand reader of 26 to 64 bits Support 8 digital inputs and 8 relay outputs 4 special outputs for lighting c...

Страница 94: ...NO4 NC3 COM3 NO3 NC2 COM2 NO2 NC1 COM1 NO1 Com A Com A DI4 DI3 DI2 DI1 Com B Com B DI8 DI7 DI6 DI5 Battery ON OFF Web Setting GND 12V Ethernet 12V D0 D1 GND A A B B Weigand GV AS100 110 GV Readers RS...

Страница 95: ...GV AS100 and GV AS110 1 2 ON GND 12V A A B B GV AS100 110 GV Readers RS 485_A TERM RS 485_B TERM Figure 4 2 Pin Function Pin Function Pin Function 12V 12V Power Supply to GV AS100 GV AS110 A GV AS100...

Страница 96: ...eter Setting 4 1 4 C Connecting GV Readers and GV GF Fingerprint Readers You can connect up to 4 units of GV Readers and GV GF1901 1902 readers to GV ASBox Multiple GV Readers and GV GF Fingerprint Re...

Страница 97: ...g Input Devices GV ASBox provides 8 inputs DI1 to DI8 All inputs are dry contact and can be configured as normally open NO or normally closed NC through the Web interface The default value is NO The f...

Страница 98: ...See To combine door access with relay activation below Figure 4 5 Outputs 1 4 Absolute Maximum Ratings Breakdown Voltage 277V AC 30V DC Continuous Load Current 5A NO 3A NC Note Absolute Maximum Ratin...

Страница 99: ...ther and connect the point on the external power supply to the NO or NC of GV ASBox based on the state of the output device NO5 COM5 NC5 NO6 COM6 NC6 Output Device External Power Supply Figure 4 6 To...

Страница 100: ...through the Web interface When the switch is set to OFF Advanced Settings are not accessible For details on Advanced Settings see 4 1 5 E Advanced Settings 4 1 4 F b Resetting the GV ASBox To reset G...

Страница 101: ...ble to the Ethernet port on GV ASBox 2 Use a computer on the same LAN with GV ASBox to assign the IP address The default address of GV ASBox is https 192 168 0 100 The default Username and Password fo...

Страница 102: ...address such as those assigned by an ISP or other DHCP server 4 1 5 A a Fixed IP Connection If your network environment supports a static IP address the wiring is illustrated as below Figure 4 8 To a...

Страница 103: ...tion including IP Address Subnet Mask Default Gateway and Domain Name Server 4 Click Submit When the setting is complete the Status field will indicate Register Success Then GV AS100 GV AS110 can be a...

Страница 104: ...V developed LocalDDNS Server can map a device name to the varying IP address of your GV AS100 GV AS110 by which the GV ASManager can access GV AS100 GV AS110 by using the device name The Local DDNS Se...

Страница 105: ...ord fields type default value admin and admin respectively Click OK The Network Configuration page Figure 4 12 appears 3 Click Enable and select Send to Local DDNS 4 In the Server IP fields type the I...

Страница 106: ...more than one GV AS Controller is connected to the GV ASManager assign each controller a different device name 2 To access the Device Name on GV ASManager open the Controller Setup dialog box and sele...

Страница 107: ...me from the website of the DDNS service provider There are 2 providers listed in GV AS100 GV AS110 GeoVision DDNS Server and DynDNS org To register at the GeoVision DDNS Server see the following instr...

Страница 108: ...in in the Re type Password field for confirmation 4 In the Word Verification section type the characters or numbers shown in the box For example type i8UCY in the required field Word Verification is n...

Страница 109: ...00 The login dialog box Figure 4 9 appears 2 In the User Name and Password fields type default value admin and admin respectively Click OK The Network Configuration page Figure 4 17 appears 3 Click En...

Страница 110: ...Device Port Keeps the default value 4000 Or modify it to match that of GV ASManager Mac Address Indicates the MAC address of the network medium Firmware Version Indicates the current firmware version...

Страница 111: ...to open the firmware file bin 3 Click the Upload button This update procedure may take 60 seconds to complete 4 When the Update is complete a dialog box appears and asks you to reboot the system Figu...

Страница 112: ...sword To change the login ID and password 1 In the left menu click Account Setting 2 On the Security Configuration page modify the login name and password The password is case sensitive and is limited...

Страница 113: ...d in GV AS100 GV AS110 set the device time and edit the input output functions The changes in some of the Advanced Setting page will effect the options available on other pages Below is a diagram draw...

Страница 114: ...to differentiate among multiple units of GV AS100 GV AS110 ID number can only be between 1 and 255 ASBox Wiegand Select the function for Wiegand Input on GV ASBox from the drop down list No Function...

Страница 115: ...ation mode for the Door Gate A Local Unlock Mode Remains open The held open state cannot be cleared through GV ASManager Local Lock Mode Remains locked The locked state cannot be cleared through GV AS...

Страница 116: ...ing lets you perform Anti Passback applications across multiple GV AS Controllers Anti Passback prevents use of a card to gain successive entries without exit to a controlled area For details on setup...

Страница 117: ...of Parameter Setting change based on your settings for Door Gate A and Door Gate B in the Function Setting page Figure 4 23 Figure 4 24 IMPORTANT Once connecting to GV AS100 GV AS110 GV ASManager wil...

Страница 118: ...s open after which the door will automatically be locked The option is only available when Door Entry Exit Control is selected Held Open Time Sets the time 5 to 9999 sec that a door gate can be held o...

Страница 119: ...ting page Figure 4 23 these options become available Option Description Held Open This alarm activates whenever the door is held open over the set period of time Forced Open This alarm activates whene...

Страница 120: ...ting page Figure 4 23 you can gain access by using the card or entering this Common Password door s password Figure 4 27 AS100 Input Name Rename the input names for the four AS100 GV AS110 inputs Clic...

Страница 121: ...cation Mode in the Function Setting page Figure 4 23 The listed number of outputs will change depending on the chosen Output Type in the In Out Function page Figure 4 31 Indicates the current input ou...

Страница 122: ...f cards currently stored in GV AS100 GV AS110 Card List Displays the list of cards stored in GV AS100 GV AS110 If there are many pages you can choose to jump to any page by entering the page number in...

Страница 123: ...V AS100 GV AS110 Local Time Disable Disable the manual configuration of time and date Setup Enable the manual configuration of Time Zone Date and Time for GV AS100 GV AS110 Daylight Savings Time DST D...

Страница 124: ...he most fitting Input Type No 3 Figure 4 32 and Input Function No 4 Figure 4 32 to describe the sensor input Through the sensor input an alarm event can be detected and it can then trigger the alarm d...

Страница 125: ...tary alarm when triggered Door A or B Fire Zone Tamper Zone Exit Button Door Contact Depending on the type of sensor and the location where it is installed select the best Input Function name to fit t...

Страница 126: ...per alarm Output Function Here you can define each output device that is connected to GV ASBox such as locking devices various alarms or Exit Button Only Output 5 to Output 8 can be connected to Light...

Страница 127: ...tting page Figure 4 23 3 Output Function Configure the output function Options available for the output function change based on your setting of Output Type above When Door Entry Exit Control is selec...

Страница 128: ...triggered when the security card is presented Entry Card Output is triggered when the card is presented to enter the parking gate Gate Exit Card Output is triggered when the card is presented to exit...

Страница 129: ...to each other through AND OR AND means that all conditions with AND must be triggered before the output is triggered OR means that only 1 of the condition with OR is needed to be triggered before the...

Страница 130: ...Button Normal Toggle Pulse Normal Lighting Toggle Lighting Pulse Lighting Door Contact Car Detection Select None to disable the condition or select between Input 1 and Input 8 to trigger the output C...

Страница 131: ...10 1 Select which door that the GV Reader GV GF Fingerprint Reader is installed 2 If you are using a GV RK1352 Reader or GV GF Fingerprint Reader type the serial number Leave the field blank if you ar...

Страница 132: ...s Max 4 readers 1 Wiegand interface 26 64 bit format Wiegand Interface 12V DC Power Supply 200mA Communication Protocol RS 485 Input 8 inputs dry contact NO NC Digital I O Output 8 outputs Operating T...

Страница 133: ...e connected to the GV ASManager and you can access the Web interface of GV AS100 GV AS110 4 2 1 Main Features Add TCP IP networking capability to GV AS100 and GV AS110 Access GV AS100 and GV AS110 s f...

Страница 134: ...t is not functional at this point 4 Ethernet Connects to the network 5 12V 12V Battery Power supply for GV AS100 GV AS110 6 RS485A RS485A Connects to GV AS100 GV AS110 7 RS485B RS485B Connects to GV R...

Страница 135: ...assignments of related connectors on the rear view of the GV ASNet for connection to GV AS100 GV AS110 Figure 4 38 Pin Function Pin Function 12V 12V Power Supply to GV AS100 GV AS110 12V GND for Powe...

Страница 136: ...B on GV ASNet You will need to connect the GV Readers or GV GF Fingerprint Readers to external power supply The figure and table shows the pin assignments for related connectors Figure 4 39 Pin Functi...

Страница 137: ...n Advanced Settings see 4 2 5 B Advanced Settings 4 2 4 C b Restoring Factory Defaults To restore factory default values press the Default button on GV ASNet for 6 seconds After this it may take up to...

Страница 138: ...n are admin Note the computer used to set the IP address must be at the same network or subnet sequence assigned to GV ASNet 3 GV ASNet is able to support two network environments Fixed IP and DHCP Se...

Страница 139: ...s ID is used by GV ASManager to differentiate among multiple units of GV AS100 GV AS110 ID number can only be between 1 and 255 Door Gate A Select the function type and authentication mode for the use...

Страница 140: ...thentication schedule of GV ASManager Fixed Card Common mode Grants access after the user presents the card or enters the door s password and ignores the authentication schedule of GV ASManager Authen...

Страница 141: ...ices 131 4 Delete MasterCard Delete Click the Delete button to delete the current MasterCard information Click Submit button to save the changes or click Cancel button to return the changes to its pre...

Страница 142: ...f Parameter Setting change based on your settings for Door Gate A in the Function Setting page Figure 4 41 Figure 4 42 IMPORTANT Once connecting to GV AS100 GV AS110 GV ASManager will load its paramet...

Страница 143: ...or remains open after which the door will automatically be locked The option is only available when Door Entry Exit Control is selected Held Open Time Sets the time 5 to 9999 sec that a door gate can...

Страница 144: ...en over the set period of time Forced Open This alarm activates whenever the door is opened by force Fire Alarm This alarm activates whenever fire is detected Access Denied This alarm activates whenev...

Страница 145: ...tion Setting page Figure 4 41 you can gain access by using the card or entering this Common Password door s password Figure 4 45 AS100 AS110 Input Name Rename the input names for the four AS100 AS110...

Страница 146: ...f cards currently stored in GV AS100 GV AS110 Card List Displays the list of cards stored in GV AS100 GV AS110 If there are many pages you can choose to jump to any page by entering the page number in...

Страница 147: ...V AS100 GV AS110 Local Time Disable Disable the manual configuration of time and date Setup Enable the manual configuration of Time Zone Date and Time for GV AS100 GV AS110 Daylight Savings Time DST D...

Страница 148: ...ader connected to GV AS100 GV AS110 Select the door that the GV Reader or GV GF Fingerprint Reader is installed and type the Serial Number found on GV Reader and GV GF Fingerprint Reader Click Submit...

Страница 149: ...d 12V 12Ah RS 485 Interface 1 RS 485 interface only for GV Readers and GV GF Fingerprint Readers Max 2 readers Communication Protocol RS 485 Operating Temperature 0 65 C 32 149 F Operating Humidity 10...

Страница 150: ...5 GV ASManager Quick Start Guide...

Страница 151: ...s of GV AS Controllers can be monitored and controlled by one GV ASManager This chapter offers a quick guide on how to install GV ASManager and how to set up controllers doors and cards For details re...

Страница 152: ...GB VGA NVIDIA GeForce 7300 GT 128MB PCI slot or ATI Radeon 9550 9600 X1050 Series 256MB AGP slot No support for onboard VGA DirectX End User Runtimes November 2008 Software NET Framework 3 5 SQL Serve...

Страница 153: ...uter and a window will pop up automatically Select Install or Remove GeoVision GV Series Driver and click Install Geovision USB Devices Driver To install the GV ASManager To run GV ASManager V2 0 or l...

Страница 154: ...would remind you of the password The features available in the dialog box Auto Login Allows auto login as the current user every time when the system is launched For security purpose this feature is o...

Страница 155: ...or the first time Select Setup MDB MSSQL Database for ASManager The Setup Database Connection dialog box appears Select Microsoft Office Access Database and click OK The program starts creating a data...

Страница 156: ...display the function windows Setup set up connected devices and schedules Personnel set up the cardholders accounts Tools set up for notification and log and Window arrange the display of different w...

Страница 157: ...and monitored events 9 Playback Plays back recorded events from a compatible GeoVision IP device 10 Live Video Displays the live view of one connected camera 11 Camera List Displays a list of connecte...

Страница 158: ...he specific dates as holidays 9 Access Groups Sets up different groups to define who can access what door at what time of a day 10 Fingerprint Access Uploads the enrolled fingerprints to the controlle...

Страница 159: ...ring a Door Define the doors on a door controller Step 3 Adding Cards Enroll cards into GV ASManager to grant access 5 4 1 Configuring a Controller 1 On the menu bar click Setup and select Device The...

Страница 160: ...ect Network and select TCP IP or LocalDDNS Type the IP address device name if LocalDDNS is selected port number login user login password and Crypto key 3DES code of the GV AS Controller Note The defa...

Страница 161: ...oor Info to configure door settings such as password lock reset time and fire action etc 3 Define the access mode by clicking the Authentication Schedule button This dialog box appears Figure 5 8 4 To...

Страница 162: ...e keypad to be granted access Card or Common Mode This mode requires the user to present the card to be granted access OR enter the door s password using the keypad to be granted access 5 The settings...

Страница 163: ...roup of cards You can also refer to Chapter 4 Settings in GV ASManager User s Manual to see how to import and export card data 5 4 3 A Adding a Single Card 1 To add one card use one of these ways Pres...

Страница 164: ...g a location e g guard When the patrol type card is presented to the reader the access will be recorded but the door will NOT unlock The feature may be set together with Privilege below The user may h...

Страница 165: ...ault setting is 1234 Privilege Assign one of these privileges to the cardholder Stop Alarm The cardholder can stop alarm sounds by presenting the card Clear Event The cardholder can clear alarm events...

Страница 166: ...box appears 2 Click the Batch New button on the toolbar This dialog box appears Figure 5 11 3 The settings in the dialog box are the same as those of adding a single card See Step 3 in the Adding a Si...

Страница 167: ...6 Troubleshooting...

Страница 168: ...correct network settings 1 Disconnect the hub or switch which connects the GV ASManager and GV AS Controller from the network 2 Give the GV ASManager a fixed IP address that is NOT used by another dev...

Страница 169: ...0 100 Figure 6 2 5 In the IP address field give the GV AS Controller an IP address that is NOT used by another device e g 192 168 0 XXX 6 On the GV ASManager enter the following settings Controller ID...

Страница 170: ...connects to the GV ASManager and GV AS Controller from the network 2 Run Windows Command Prompt Take Classic Windows Start Menu for example click Start select Accessories and click Command Prompt 3 T...

Страница 171: ...on 1 Q4 The GV ASManager cannot retrieve the video from the DVR for playback 1 Make sure the Remote ViewLog Service on Control Center Server is enabled on the DVR 2 Make sure the time on the GV ASMana...

Страница 172: ...RS 485 interface 1 Make sure the GV Reader is correctly wiring to the GV AS Controller and Switch 4 on the GV Reader is set to OFF 2 Make sure the correct GV Reader ID is set on the GV AS Controller Q...

Отзывы: