General
Be sure the available power is the same voltage and phase as that
shown on the unit serial plate. Line and low voltage wiring must be
done in accordance with local codes or the National Electric Code,
whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 of the
contactor as shown below for single-phase unit. Consult the unit’s
Electrical Data for correct fuse sizes.
Open lower front access panel. Insert power wires through
knockouts on lower left side of cabinet. Route wires through left
side of control box and connect to contactor and ground. Close
lower front access panel before unit start-up.
Line Voltage 208-230/60/1 Control Box
Electrical Connections
Pump Wiring 208-230/60/1
Position the thermostat subbase against the wall so that it is
level and the thermostat wires protrude through the middle of the
subbase. Mark the position of the subbase mounting holes and
drill holes with a 3/16-inch bit. Install supplied anchors and secure
base to the wall. Thermostat wire must be 8-conductor, 18-AWG
wire. Strip the wires back 1/4-inch (longer strip lengths may cause
shorts) and insert the thermostat wires into the connector as
shown. Tighten the screws to insure secure connections. The
thermostat has the same type connectors, requiring the same
wiring. See instructions enclosed in the thermostat for detailed
installation and operation information.
Electronic Thermostat Installation
208 Volt Operation
All ECO-Y 208/230 units are factory wired for 230 volt operation.
For 208 volt operation, the red and blue transformer wires must be
switched on terminal strip PS.
Pump Wiring
See Pump Wiring figure below for electrical connections
from control box to pumps.
R
Y1
C
O
G
L
W
24VAC (Hot)
24VAC (Common)
Compressor
Reversing Valve
Blower Relay
System Monitor
Aux. Heat
Terminal Block (TB)
Thermostat
R
C
Y1
O
G
L
W1
Thermostat Wiring
CC
PS
3 1 2
TB
Loop Pump
Power
Thermostat
Connections
L2 L1
Line Voltage
Ground
Ground