OVATION™ Series 

Automatic Transfer Switch Systems 

Installation, Operating and Maintenance Instructions 

 

For Models: 

 

ATS1001D, ATS1001R 

 

ATS2001D, ATS2001R 

 

ATS2002R 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Model ATS1001D       Model ATS1001R      Model ATS2001D          Model ATS2001R 

    Model ATS2002R 

 
 

NOTE TO INSTALLER:  Please leave this manual with the customer for future reference. 

Una versión en español de este manual está disponible para descargar en nuestra página web www.gen-

tran.com/support/installation 

 

 
MODEL NUMBER ___________________________________SERIAL NUMBER ________________________________________________________ 
 
DATE OF INSTALLATION ______________________________DEALER NAME/PHONE ___________________________________________________ 
 

Please note your model number and serial number here for future reference. The serial number may be found inside the 
enclosure, lower left or right.

 

 
 

 
 

OVATION™ Series Automatic Transfer Switches should NOT be used for Emergency Systems 

(See NEC Articles 517 and 700), nor as a Legally Required System (see NEC Article 701), nor for 

primary power in place of the electric utility or in life support applications. 

Содержание OVATION ATS1001D

Страница 1: ...n MODEL NUMBER ___________________________________SERIAL NUMBER ________________________________________________________ DATE OF INSTALLATION ______________________________DEALER NAME PHONE __________...

Страница 2: ...roduct or property damage This symbol refers to a hazard or unsafe practice that can result in severe personal injury or death This symbol warns of immediate hazards that will result in severe persona...

Страница 3: ...TS 20 4 4 Connecting the Low Voltage Cable to the Generator 21 4 5 Installing and Wiring PowerPause Load Management Modules 21 SECTION 5 PROGRAMMING THE SYSTEM 23 5 1 Setting Generator Size 23 5 2 Set...

Страница 4: ...ure Eliminates the need for a separate sub panel significantly reduces installation time expense and complexity Load center accepts interchangeable type circuit breakers from Siemens Square D Cutler H...

Страница 5: ...e 22K 22K 10K 22K available Dimensions HxWxD 24 x14 31 x3 93 28 x14 5 x4 25 42 x14 31 x3 93 41 x14 5 x4 25 23 5 x18 5 x4 25 Weight LBS 28 27 46 43 23 22K AIC rating available order 22 suffix It is ina...

Страница 6: ...ait for possible successful utility power grid re strike approx 15 seconds before the load is transferred to generator power At the time of load transfer to generator power all appliances connected to...

Страница 7: ...rPause connected appliances again 4 During the utility power failure the generator will continue to power the load until it either runs out of fuel gasoline propane or diesel powered gensets or until...

Страница 8: ...odel LSM Not shown ATSRK Relay Kit Control Module Generator Main 200 Amp Drive Motor Assembly Neutral Bar Ground Bar Circuit Breaker Spaces 4 To Set Generator Size To Set Exercise Schedule Model ATS20...

Страница 9: ...uit breakers are mechanically interlocked to prevent simultaneous UTILITY and GENERATOR power source feeds Interlocks are automatically moved by a computer controlled actuator and motor which may move...

Страница 10: ...20or 30 amp circuit breakers is designed to protect devices connected to the transfer from surges coming in from the power lines 1 6 Standards Compliance OVATION Series ATS systems have been tested a...

Страница 11: ...m content support installation_instructions asp see Ovation Series ATS Generator Connection Diagrams for additional information 2 2 Compatible Circuit Breakers Each OVATION Series ATS has been configu...

Страница 12: ...RK for generator control See Section 2 1 if required 3 2 Unpacking Inspection After unpacking carefully inspect the transfer switch for shipping damage Shipping Damage is not warranted Contact the fre...

Страница 13: ...y position 1 with the air handler continuously connected to generator power air will continue to circulate within the house Continuing with the example let s say the second priority appliance is a 30...

Страница 14: ...agement Module and Relay Box are Refrigerators and freezers Aquariums Central heating systems gas oil electric Furnace fan air handler Sump pumps Septic lift pumps Pool and spa anti freeze pumps Medic...

Страница 15: ...damage or a future malfunction This device should be installed in accordance with all local codes standards and regulations and the latest edition of the National Electrical Code Do not allow petroleu...

Страница 16: ...16 INTERNAL WIRING DIAGRAMS MODELS ATS2001D R Diagram 4 2...

Страница 17: ...17 INTERNAL WIRING DIAGRAMS MODEL ATS2002R Diagram 4 3...

Страница 18: ...de proper protection to conductor insulation For more information on wire size and ampacity ratings see NEC Article 310 Table 310 16 The OVATION Series ATS have been UL Listed for use with Copper or A...

Страница 19: ...per or AL wire 6 Install and connect appropriately sized wire from the generator to the terminals marked GENERATOR MAIN If installing the Current Sense Cable provided with the optional PowerPause Load...

Страница 20: ...nsfer switch on the control module There is a small black 4 position terminal connector delivered plugged into J6 on the Control Module that is labeled to indicate how to connect the low voltage cable...

Страница 21: ...odule from transfer switch Refer to Figure 4 1 1 3 a Remove branch circuit breaker if installed opposite controller module b Slide Control Module towards circuit breaker bus stabs towards center of en...

Страница 22: ...a Line up Control Module to breaker bus stabs from where removed in step 1 b Hold at 30 angle push onto bus stabs c Lower outside end flush with enclosure d Slide Control Module towards enclosure out...

Страница 23: ...ERATOR EXERCISE SCHEDULE and use provided small straight blade screwdriver to rotate the dial to the desired schedule See Table 5 2 to determine model Once set the OVATION Series ATS will initiate a g...

Страница 24: ...TOP Starts and stops generator To start generator press once To stop generator press twice Will override all generator and transfer switch time delays EXERCISE Starts generator exercise cycle During t...

Страница 25: ...system switch key to ON 6 Set generator AUTO MANUAL OFF switch to AUTO 7 Press SERVICE button Generator start sequence will begin and runs for 5 minutes 6 3 Testing the Transfer Switch 1 Turn OFF the...

Страница 26: ...load is disqualified and not allowed to operate on generator power Note the LED fast flash condition 8 Steps 5 7 will be automatically repeated for each detected load LED 1 5 will flash for priority 6...

Страница 27: ...out of range 4 Utility power restored genset power not required 5 Total loads exceed 85 of genset continuous rating 6 Largest load exceeds genset continuous rating 1 Reset circuit breaker on genset 2...

Страница 28: ...ing 1 Battery may be defective 2 Incorrect battery charger output 1 Check battery voltage a reading of 8 VDC or less after 24 hours of charging indicates that battery needs replacement 2 Check battery...

Страница 29: ...cover products that have been subject to misuse or unauthorized repair NOTE TO INSTALLER Please provide your company name and phone number inside the front door so that the customer will be able to co...

Страница 30: ...D modified Siemens 20 20 B 22 2 51008 Circuit breaker 100A 2 pole 120 240V 10K AIC B 22 22 1 510081 Circuit breaker 100A 2 pole 120 240V 22K AIC B 23 1 51037 Warranty Reply Card Product Registration n...

Страница 31: ...19 22 1 510081 Circuit breaker 100A 2 pole 120 240V 22K AIC B 20 1 51037 Warranty reply card not shown A 21 1 51080 Options Order Sheet not shown A 22 1 51147 Label GENTRAN silver green 340 not shown...

Страница 32: ...d loadcenter 40 40 B 20 1 51037 Warranty reply card not shown A 21 1 51102 Circuit breaker 125A 2 pole 120 240V B 22 1 51147 Label GENTRAN silver green 340 not shown A 23 1 72006 Label Gen Util not sh...

Страница 33: ...cuit breaker 125A 2 pole 120 240V 10K AIC B 21 1 51147 Label GENTRAN silver green 340 not shown A 22 1 72006 Label Gen Util not shown A 23 2 72009 Label SN not shown A 24 1 72010 Label SN controller n...

Страница 34: ...8AWG B 25 1 51037 Warranty reply card not shown A 26 1 51080 Options Order Sheet not shown A 27 2 51101 Circuit breaker 200A 2 pole 120 240V 10K AIC B 27 22 1 511011 Circuit breaker 200A 2 pole 120 24...

Страница 35: ...p 2 circuits 240 VAC Includes 2 relays PP50 1 PowerPause Relay Box 50 Amp 1 circuit 240 VAC Includes 1 relay PP50 2 PowerPause Relay Box 50 Amp 2 circuits 240 VAC Includes 2 relays ATSRK Relay Kit One...

Страница 36: ...ran com Customer Service Hours 8 00 a m until 5 00 p m Eastern Time Monday Friday 07 16 10 PN 530001 Rev D Copyright 2008 2010 Gen Tran Corporation All rights reserved GenTran and the GenTran Logo are...