background image

Near fluorescent light fixtures.

Electrical "noise" from nearby fluorescent

light fixtures may cause a nuisance alarm.

Install alarms and fluorescent

light on separate electrical circuits

Never disconnect an AC alarm to silence a nuisance

alarm. Use a cold damp rag or sponge and apply to the heat sensor

(silver disk) on the face of the unit. The alarm will automatically turn off

when the temperature of the sensor falls below 135oF. Do not

unnecessarily stand close to the alarm. The sound produced by the

alarm is loud because it is designed to awaken you in an emergency.

Prolonged exposure to the horn at a close distance may be harmful to

your hearing.

INSTALLATION OF HD135

New Construction: alarm head should not be installed until

AFTER

painting

and construction are finished and cleaned up.

MOUNTING OUTLET BOX

Use a 2" x 3" switch box or a 4" square or octagon junction box. Mount a box

for each alarm. If wall mounting is desired, be sure the box screws are

oriented to upper right and lower left corners. Be sure to use supplied

Mounting Plate.

WIRING/GENERAL

1. Use ANSI/UL Listed cable with Class1 insulation.

2. Observe local code requirements. Use the box clamps to anchor cable to

outlet box.

3. Metal outlet boxes must be grounded to earth ground.

4.

NOTICE:

USE ONLY DURACELL

®

MN 1604 BATTERY WITH THE HD135

HEAT ALARM.

CAUTION

: Turn off electricity to prevent SHOCK and damage to alarm. Be

sure the power line to the alarm is

not

controlled by any on/off switch, or other

type of switch, other than a fuse or circuit breaker.

IMPORTANT:

Insure that all fluorescent lighting fixtures are properly grounded.

NOTICE:

THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH

THE PROVISIONS OF ARTICLE 300.3 (B) 210 OF THE NATIONAL

ELECTRICAL CODE, NFPA 70. WIRE INSTALLATION SHOULD BE

PERFORMED ONLY BY A LICENSED ELECTRICIAN.

WIRING ONE HEAT ALARM

1. Run a minimum of 16 gauge, 2-conductor cable, plus ground (3 wires) to

the alarm junction box from a power supply. Use ANSI/UL Listed Class

1 wire.

NOTICE:

THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH

THE PROVISIONS OF ARTICLE 300.3(B) 210 OF THE NATIONAL

ELECTRICAL CODE, NFPA 70.

2. Make wire connections to the supplied plug-in connector as follows: black to

black, white to white, and connect the ground wire to the metal outlet box.

PLUG

HEAT

ALARM

BLK-120VAC

L1-220VAC

1

WHT-120VAC

L2-220VAC 

11

RED / YEL

10

HOT

NEUT

POWER

TANDEM

550-0158

Pg. HD-4

FIGURE 6

FIGURE 5: A SMOKE ALARM MUST BE LOCATED ON EACH LEVEL IN

ADDITION TO EACH BEDROOM.

IMPORTANT CONSIDERATION

NFPA 72, 2010 Edition, Chapter 29, Section 29.8.1.4(5)(b) states:

“Smoke alarms installed in one- and two-family dwellings shall not

remain in service longer than 10 years from the date of manufacture.”

Smoke alarms should be replaced for the following reasons:

Dust, dirt, and other environmental contaminants can affect your smoke

and heat alarm over a prolonged period.

Fast changing industry consensus standards and codes on all smoke and

heat alarms make it advisable to periodically upgrade your devices to

maximize life safety.

Assurance that your smoke and heat alarm needs are kept abreast with the

constantly improving electronic technology.

Smoke and heat alarms are recognized as one of the lowest cost ways to

protect dwelling inhabitants against the danger of fire(s). It makes good

common sense to periodically replace and update your smoke alarm that

contributes so much to life safety.

MOUNTING LOCATION

This heat alarm can be mounted on a ceiling or wall with equal efficiency in

either location.

Ceiling location

-heat alarm should be mounted at least 4 inches (100

mm) from a wall.

Wall location

-locate the top of the heat alarm not less than 4 inches (100

mm) or more than 12 inches (300mm) from the ceiling.

FIGURE 5

FIGURE 6: RECOMMENDED HEAT ALARM MOUNTING LOCATIONS
The placement of the alarm is critical if maximum speed of fire detection is

desired. Thus, a logical location for a alarm is the center of the ceiling. At this

location, the alarm is closest to all areas of the room.

LOCATIONS TO AVOID

Placing heat alarms where they will not operate properly causes nuisance

alarms.

To avoid nuisance alarms, do not place heat alarms:

Where temperatures are regularly below 40

o

F (4.44

o

C) or above 100

o

F

(37.78

o

C).

In air streams passing by kitchens.

It is possible normal air currents

can draw cooking heat into the sensor of a unit near the kitchen. If you

experience frequent unwanted alarms from a unit near your kitchen, try

relocating it. Do not install your heat alarm over a stove or a range.

In dead air spaces at the top of a peaked roof or in the corners

between ceilings and walls.

Dead air may prevent heat from reaching a

alarm. See FIGURES 1 and 6 for recommended mounting locations.

NOTICE

: RED-YELLOW WIRE: THE RED-YELLOW WIRE FROM THE HEAT

ALARM IS FOR TANDEM CONNECTION ONLY. DO NOT USE, AND DO

NOT REMOVE INSULATION CAP UNLESS CONNECTING ANOTHER HEAT

ALARM.

Отзывы: