57
NOTE:
The power supply can accept values higher by 5% than the table values, however it
is not recommended to program the power supply over the rated values.
7.7.7 Status control commands
Refer to section 7-8 for definition of the registers.
Command
#
Description
1
STT?
Reads the complete power supply status.
Returns ASCII characters representing the following data, separated by commas:
Table 7-5: OVP programming range
Table 7-6: UVL programming range
Model
Rated Output Voltage (V)
Minimum
(V)
Maximum
(V)
8
10
16
20
30
40
60
80
100
150
300
600
0.5
0.5
1.0
1.0
2.0
2.0.
5.0
5.0
5.0
5.0
5.0
5.0
10.0
12.0
19.0
24.0
36.0
44.0
66.0
88.0
Model
Rated Output Voltage (V)
Minimum
(V)
Maximum
(V)
8
10
16
20
30
40
60
80
100
150
300
600
0
0
0
0
0
0
0
0
0
0
0
0
7.60
9.50
14.3
19.0
28.5
38.0
57.0
76.0
95.0
142
285
570
MV<actual (measured) voltage>
PV<programmed (set) voltage>
MC<actual (measured) current>
PC<programmed (set) current>
SR<status register, 2-digit hex>
FR<fault register, 2-digit hex>
Example response: MV(45.201),PV(45),MC(4.3257),PC(10),SR(30),FR(00)
Reads Fault Conditional Register. Return 2-digit hex.
Set Fault Enable Register using 2-digit hex.
Reads Fault Enable Register. Returns 2-digit hex.
Reads Fault Event Register. Returns 2-digit hex. Clears bits of Fault Event Register.
Reads Status Conditional Register. Returns 2-digit hex.
Sets Status Enable Register using 2-digit hex.
Reads Status Enable Register. Returns 2-digit hex.
Reads Status Event register. Returns 2-digit hex. Clears bits of Status Event register.
2
3
4
5
6
7
8
9
FLT?
FENA
FENA?
FEVE?
STAT?
SENA
SENA?
SEVE?
Minimum
(A)
Model
Maximum
(A)
GEN8-600
GEN10-300
GEN16-310
GEN20-250
GEN30-170
GEN40-125
GEN60-85
GEN80-65
GEN100-50
GEN150-34
GEN300-17
GEN600-8.5
000.00
000.00
000.00
00.00
00.00
00.00
00.000
00.000
00.000
00.000
0.000
0.000
600.00
300.00
310.00
250.00
170.00
125.00
85.000
65.000
50.000
34.000
17.000
8.500
Current programming range
Table 7-4:
110
165
330
660