60
Figure 61:
HTTP
– Event Editor / Test
After you have clicked the “Test” button (Attention! The shutdown will be executed immediately
without consideration of the defined delay), the following message will be displayed:
Figure 62:
HTTP
– Job Test Page
You can see the successful sending of the signal into the “AlarmLog”:
Figure 63:
HTTP
– AlarmLog
4.4.5
Automatic Reset of the Redundancy Alarm
You can use the function „Send RCCMD cancel shutdown“, to discard a previously sent
shutdown automatically. If a shutdown was suppressed, because of the existing redundancy at
this point of time, but the problem was solved at the UPS intermediate, you can reset the
shutdown with the function „Send RCCMD cancel shutdown“. The client, which received the
shutdown, will be encouraged to reset it.
This command can be set individually into your CS121, UPSMAN or BACS WEBMANAGER
Events/Alarms configuration, but makes sense only, if the event, which will send the command,
is true, if the UPS is back in normal condition. For this the eve
nts „POWER RESTORED“,
„BATTERY LOW OFF“, „UPSMAN STARTED“ and „GENERAL ALARM OFF“ are suitable, if
they are provided from your UPS into the CS121. The job „Send RCCMD cancel shutdown“
would be set into these all-clear events, so that e. g. at restart of th
e UPS, the event „UPSMAN
STARTED“ would reset the accordant RCCMD client automatically.
Alternative: Should the job „Send RCCMD cancel shutdown“ not be present into your CS121,
UPSMAN or BACS WEBMANAGER, you can use the job „Send RCCMD shutdown to remote
c
lient“ or rather „Send RCCMD execute to remote client“ alternatively.