2005.08.23

- 7 -

Indoor EEPROM abnormal
Outdoor EEPROM abnormal
Indoor room temperature sensor
open
Indoor room temperature sensor
short-circuited
Indoor heat exchanger temperature
sensor open
Indoor heat exchanger temperature
sensor short-circuited
Float switch operated
Indoor signal abnormal
Outdoor signal abnormal
Indoor fan abnormal
Outdoor power source connection
abnormal
Outdoor heat exchanger
temperature sensor open
Outdoor heat exchanger
temperature sensor short-circuited
Outdoor temperature sensor open
Outdoor temperature sensor
short-circuited
Outdoor discharge pipe temperature
sensor or compressor temperature
sensor open
Outdoor discharge pipe temperature
sensor or compressor temperature
sensor short-circuited
Outdoor high pressure abnormal

Outdoor discharge pipe temperature
or compressor temperature sensor
abnormal

OPERATION

lamp (RED)

(2 times)

(2 times)

(3 times)

(3 times)

(4 times)
(5 times)
(5 times)
(6 times)

TIMER lamp

(GREEN)

(2 times)

(3 times)

(3 times)

(4 times)

(4 times)

(5 times)

(5 times)

(6 times)

(7 times)

SWING lamp

(ORANGE)

 : 0.1s ON/0.1s OFF (flash)

 : OFF

 : 0.5s ON/0.5s OFF (flash)

Error contents

Operation can be checked by lighting and flashing of the
display section OPERATION, TIMER, and VERTICAL SWING
lamps.
Perform judgment in accordance with the following.

TEST RUNNING

When the air conditioner is run by pressing the remote control
unit test run button, the OPERATION, TIMER, and VERTICAL
SWING lamps flash slowly at the same time.

ERROR 

The OPERATION, TIMER, and VERTICAL SWING lamps
operate as follows according to the error contents.

1. INDOOR  UNIT

SWING SWING

TIMER

MANUAL

AUTO

OPERATION

VERTICAL SWING lamp (Orange)
TIMER lamp (Green)

OPERATION lamp (Red)

flash

1flash

2 flash

3 flash

 4 flash

5 flash

6 flash

7 flash

8 flash

9 flash

10 flash

flash

Lighting

Lighting

Lighting

Lighting

Lighting

Lighting

Lighting

Lighting

Lighting

Lighting

Model abnormal or EEPROM abnormal

Power source connection error

Discharge temp. sensor error

Heat exchanger temp. sensor error

Outdoor temp. sensor error

Communication signal error

Indoor unit error

Discharge temp. abnormal

High pressure abnormal

Compressor temp. abnormal

Compressor temp. sensor error

No error. Protect operation

Dislighting

2. OUTDOOR UNIT LEDS

Heat & Cool model (reverse cycle) only

When a malfunction occurs in the out-
door unit, the LEDs on the circuit board
light to indicate the error. Refer to the
following table for the description of
each error according to the LEDs.

LED1

LED2

Error contents

When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pres-
sure abnormal, the LED lamp lights continuously for 24 hours, as
long as the power is not turned off.

LED2 LED1

LED layout

E R R O R   C O N T E N T S

Содержание ABG54FBAG

Страница 1: ...OOR PRINTED CIRCUIT BOARD CIRCUIT DIAGRAM 8 OUTDOOR PRINTED CIRCUIT BOARD CIRCUIT DIAGRAM 10 DISASSEMBLY ILLUSTRATION 11 PARTS LIST 23 STANDARD ACCESSORIES 26 SPLIT TYPE ROOM AIR CONDITIONER CEILING t...

Страница 2: ...ING COOLING 9 5 CURRENT A HEATING 9 5 INPUT WATTS kW COOLING 5 16 HEATING 5 30 E E R kW kW COOLING 2 81 HEATING 3 11 MOISTURE REMOVAL hr 6 0 AIR CIRCULATION m3 hr 2 200 FAN MOTOR TYPE Hermetic type 2...

Страница 3: ...2005 08 23 D I M E N S I O N S 1 660 240 700 1 600 130 300 Unit mm Models ABG54FBAG ABG54UBAG ABY54FBAG ABY54UBAG 2...

Страница 4: ...2005 08 23 31 77 900 330 12 9 21 1 290 400 650 370 Air Flow 151 170 99 196 Models AOG54FMAYT AOG54UMAYT AOY54FMAYT AOY54UMAYT 3 Unit mm...

Страница 5: ...CHECK VALVE HIGH PRESSURE SWITCH Charging Valve Charging Valve OUTDOOR UNIT INDOOR UNIT Refrigerant pipe 19 05mm 3 4 COOL EVAPORATOR Refrigerant pipe 9 52mm 3 8 Charging valve Charging Valve ACCUMULAT...

Страница 6: ...2005 08 23 5 C I R C U I T D I A G R A M Models ABG54FBAG ABY54FBAG Models AOG54FMAYT AOY54FMAYT...

Страница 7: ...2005 08 23 6 Models ABG54UBAG ABY54UBAG Models AOG54UMAYT AOY54UMAYT...

Страница 8: ...following TEST RUNNING When the air conditioner is run by pressing the remote control unit test run button the OPERATION TIMER and VERTICAL SWING lamps flash slowly at the same time ERROR The OPERATIO...

Страница 9: ...2 UL1430 AWG24 UL1430 AWG24 GRAY GRAY GRAY GRAY ROOM TEMPERATURE THERMISTOR PIPE TEMPERATURE THERMISTOR 14V 14V IC5 1 7 uPA2003GR IC4 7 7 uPA2003GR 9 16 1 6 11 14 16 3 1 2 4 5 7 10 12 13 15 9 76 77 35...

Страница 10: ...P127 P65 P66 P02 XT2 P64 P63 P62 P61 P60 P120 P37 P35 P67 P30 P31 P32 P34 P121 P33 P40 P41 P42 RESET P23 P24 I C XT1 P03 P43 P44 P45 P46 P47 P00 P12 P13 P14 P36 P131 P72 P71 P70 P01 P55 P54 P53 P52 P...

Страница 11: ...ACK CN11 3 BLACK CN11 4 BLACK CN11 5 BROWN CN11 6 BROWN 6 5 4 3 2 1 CN1 1 CN1 3 CN1 2 BLACK WHITE RED BLUE UL1015 AWG20 BLACK UL1015 AWG20 BLACK UL1015 AWG20 BLACK UL1015 AWG20 BLACK 4 WAY VALVE UL101...

Страница 12: ...ABG54UBAG ABY54FBAG ABY54UBAG 382 761 387 12 386 684 138 735 752 146 329 396 868 63 160 361 321 69 228 407 505 408 435 434 229 580 743 240 383 762 286 122 403 8 174 126 388 164 174 181 403 122 286 384...

Страница 13: ...2005 08 23 407 434 435 408 505 506 69 876 1 12...

Страница 14: ...2005 08 23 387 160 91 91 91 321 386 361 13...

Страница 15: ...2005 08 23 63 868 385 763 227 321 387 436 424 684 438 876 2 14...

Страница 16: ...2005 08 23 15 186 187 195 34 253 3 253 7 253 5 253 4 253 6 253 9 253 2 185 1 815 1 381 4 380 236 982 1 982 2 223 875 448 234 195 472 625 Models ABG54FBAG ABY54FBAG 253 1...

Страница 17: ...2005 08 23 16 Models ABG54UBAG ABY54UBAG 253 3 34 195 253 4 253 5 253 6 253 7 236 234 185 1 625 187 472 448 380 381 4 186 223 982 2 815 1 982 1 875 253 1 253 2...

Страница 18: ...2005 08 23 Models AOG54FMAYT AOG54UMAYT AOY54FMAYT AOY54UMAYT 3 2 5 31 1 6 4 3 17...

Страница 19: ...2005 08 23 15 16 14 13 7 8 9 10 11 12 Models AOG54FMAYT AOG54UMAYT AOY54FMAYT AOY54UMAYT 18...

Страница 20: ...2005 08 23 Models AOY54FMAYT AOG54FMAYT 38 18 15 17 39 16 20 23 25 19...

Страница 21: ...2005 08 23 Models AOY54UMAYT AOG54UMAYT 21 20 19 18 17 16 15 25 24 29 22 23 20...

Страница 22: ...2005 08 23 Models AOY54FMAYT AOG54FMAYT 37 36 35 34 34 28 21...

Страница 23: ...2005 08 23 Models AOY54UMAYT AOG54UMAYT 28 26 27 35 34 34 22...

Страница 24: ...mperature Thermistor 9703299025 9703299025 9703299025 9703299025 Pipe Temperature Thermistor 9900022020 9900022020 9900022020 9900022020 Thermistor Spring A 313728262708 313728262708 313728262708 3137...

Страница 25: ...59712008 9359712008 505 Louver Stopper 9359724001 9359724001 9359724001 9359724001 506 Louver Rod 9359725008 9359725008 9359725008 9359725008 580 Top Cover 9359737001 9359737001 9359737001 9359737001...

Страница 26: ...Assy 9371615011 9371615011 9371615011 9371615011 19 Solenoid 9900165055 9900165055 20 Pressure Switch 9900276010 9900276010 9900186012 9900186012 21 4 Way Valve 9970035012 9970035012 22 Discharge Temp...

Страница 27: ...313806350303 VT wire For indoor side pipe joint large pipe 2 1 9350716029 9374714049 Coupler heat insulator large For indoor side pipe joint small pipe 4 9352766015 Coupler heat insulator small For f...

Страница 28: ...2005 08 23 March 2005 Printed in Japan 0503J2773...

Отзывы: