5
Starting the Generator
1) Manual Pull Start
a) Disconnect any load from the A.C.
socket.
b) Shut off the A.C. breaker.
c) Turn the fuel valve to the “ON”
position.
d) Put the choke handle in the “ON”
position.
i) When engine is warm the choke
is not necessary.
e) Flip the engine switch to the “ON”
position.
f) Slightly pull the pull-start handle until
feeling resistance. Then pull handle
forcefully.
i) Do not let the pull handle go to
return freely. Return it back by
hand to avoid damage to the
recoil mechanism.
g) Repeat process as needed.
h) Turn choke off when engine is warm.
Engine Operation Methods
To keep your generator set in optimum
mechanical and electrical condition, please
apply the following:
Starting Rating
Equipment
Start
Rating
Resistive
Load x1 x1
Filament lamp,
TV set
100W
100W 100W
Capacitive
Load x2
x1.5
Fluorescent
Light, metal-
halide lamp
Load
Selection
Multiple
Inductive
Load
x3-5 x1.5
Refrigerator,
electric fan,
electric range
150W
450
300W
1) When more than two loads are
connected to the generator set, switch
on the largest current load first and
switch on loads one at a time.
2) Only qualified electrical personnel
should connect generator to household
power supply.
3) Inspect the connections of the generator
before the loads are applied. If the
connections are not correct the
generator can be damaged or cause
fire.
4) After connecting the electric devices,
switch the A.C. breaker to the “ON”
position. Operating the generator with
breaker held in position or starting the
generator with load is forbidden.
5) Overload current will automatically shut
off the A.C. breaker. If breaker shuts
off, disconnect the load and wait for one
minute before reconnecting the load.
Stopping the Engine
1) Cut off the A.C. breaker
2) Turn off the engine switch
3) Remove any load
4) Shut off the fuel valve