Lynx Rooftop 1800 AC User Manual
4.
TROUBLESHOOTING
All work on the unit should be carried out by qualified
and certified individual. If unit is not performing as expected, or
display is showing a fault code – stop using the unit and refer to
a professional. Do not perform any work without proper tools
and training.
4.1
Troubleshooting of Common Problems
Symptom
Cause
Remedy
The compressor
does not start or
starts and stops
frequently (short
cycles)
The voltage is too high or low
Bring voltage to specified
voltage range
Power supply cable is undersized
Use proper gauge supply lines
Incorrect temperature setting
Set temperature
Refrigerant leak in system
Repair leak and add refrigerant
Poor cooling
performance
Condenser and/or evaporator coils
are clogged with dust
Fans or airways obstructed
Clean filter and condenser
Inspect the heating exchange of
the condenser
The air
conditioner does
not power on
The fuse in open
Voltage too low
The wiring or plug-in connector is
not connected well
Check and replace the fuse
Provide adequate voltage
Verify, reseat connections
Air conditioner
drains the battery
faster than
expected
Battery depleted or capacity is
too low
Repair or upgrade the battery
Содержание 1800
Страница 1: ......
Страница 7: ...info generalcomponents ca 1 800 517 7740 2 PRINCIPLE OF OPERATION 2 1 Electrical Diagram ...
Страница 8: ...7 Lynx Rooftop 1800 AC User Manual 2 2 Plumbing Diagram ...
Страница 12: ...11 Lynx Rooftop 1800 AC User Manual ...
Страница 15: ...info generalcomponents ca 1 800 517 7740 Front of the vehicle ...
Страница 20: ...19 Lynx Rooftop 1800 AC User Manual The unit should not be used at temperatures below 5 41 or above 43 110 ...
Страница 23: ...info generalcomponents ca 1 800 517 7740 ...
Страница 24: ...23 Lynx Rooftop 1800 AC User Manual ...
Страница 25: ...info generalcomponents ca 1 800 517 7740 ...
Страница 26: ...25 Lynx Rooftop 1800 AC User Manual ...
Страница 27: ...info generalcomponents ca 1 800 517 7740 ...