¥   Unless otherwise specifically permitted in the NEC, the over current protection for conductor types marked with an ¥ shall not exceed 15 amperes for No. 

14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum 
after any correction factors for ambient temperature and number of conductors have been applied.

  SIZE 

TEMPERATURE RATING OF CONDUCTOR 

SIZE

 

 

60° C 

75° C 

90° C 

60° C 

75° C 

90° C

 

 

(140° F) 

(167° F) 

(194° F) 

(140° F) 

(167° F) 

(194° F)

  

TYPES 

TYPES 

TYPES 

TYPES 

TYPES 

TYPES

 

 

TW¥, UF¥ 

FEPW¥ 

TA, TBS, SA 

TW¥ 

RH¥, RHW¥ 

TA, TBS

 

 

 

RH¥, RHW¥ 

SIS, FEP¥ 

UF¥ 

THHW¥ 

SA, SIS,

 AWG 

 

THHW¥ 

FEPB¥ 

 

THW¥ 

THHN¥ 

AWG

 kcmil 

 

THW¥ 

RHH¥, RHW2 

 

THWN¥ 

THHW¥

 

 

 

THWN¥ 

THHN¥, THHW¥ 

 

XHHW¥ 

THW2, THWN2

 

 

 

XHHW¥ 

THW2, THWN2 

 

USE¥ 

RHH¥, RHW2

 

 

 

USE¥, ZW¥ 

USE2, XHH 

 

 

USE2

  

 

 

XHHW¥ 

 

 

XHH, 

XHHW

 

 

 

 

XHHW2, ZW2 

 

 

XHHW2, ZW2

 

COPPER 

ALUMINUM OR COPPER CLAD ALUMINUM

 18 

— 

— 

14 

— 

— 

— 

 16 

— 

— 

18 

— 

— 

— 

 14 

20¥ 

20¥ 

25¥ 

— 

— 

— 

 12 

25¥ 

25¥ 

30¥ 

20¥ 

20¥ 

25¥ 

12

 10 

30 

35¥ 

40¥ 

25 

30¥ 

35¥ 

10

 8 

40 

50 

55 

30 

40 

45 

8

 6 

55 

65 

75 

40 

50 

60 

6

 4 

70 

85 

95 

55 

65 

75 

4

 3 

85 

100 

110 

65 

75 

85 

3

 2 

95 

115 

130 

75 

90 

100 

2

 1 

110 

160 

150 

85 

100 

115 

1

 1/0 

125 

150 

170 

100 

120 

135 

1/0

 2/0 

145 

175 

195 

115 

135 

150 

2/0

 3/0 

165 

200 

225 

130 

155 

175 

3/0

 4/0 

195 

230 

260 

150 

180 

205 

4/0

 250 

215 

255 

290 

170 

205 

230 

250

 300 

24 

285 

320 

190 

230 

255 

300

 350 

260 

310 

350 

210 

250 

280 

350

 400 

280 

335 

380 

225 

270 

305 

400

 500 

320 

380 

430 

260 

310 

350 

500

 600 

355 

42 

475 

285 

340 

385 

600

 700 

385 

460 

520 

310 

375 

420 

700

 750 

400 

475 

535 

320 

385 

435 

750

 800 

410 

490 

555 

330 

395 

450 

800

 900 

435 

520 

585 

355 

425 

480 

900

 1000 

455 

545 

615 

375 

445 

500 

1000

 1250 

495 

590 

665 

405 

485 

545 

1250

 1500 

520 

625 

705 

435 

520 

585 

1500

 1750 

545 

650 

735 

455 

545 

615 

1750

 2000 

560 

665 

750 

470 

560 

630 

2000

TABLE 4 —  ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS RATED 0-2000 VOLTS, 60° TO 90° C (140° TO 194° F). 

NOT MORE THAN THREE CONDUCTORS IN RACEWAY OR CABLE OR EARTH (DIRECTLY BURIED), BASED ON 

AMBIENT TEMPERATURE OF 30° C (86° F) (REFERENCE NEC TABLE 310-16)

Operation

Содержание Stationary Emergency Generator

Страница 1: ...This manual should remain with the unit Not intended for use in critical life support applications OUTDOOR INSTALLATION ONLY Installation Manual Stationary Emergency Generator ...

Страница 2: ...Systems 7 1 9 Calculating Volumetric Flow Rate and Pipe Size 10 1 10 Electrical Connections 13 1 11 Battery Installation 13 1 12 Generator Activation 14 INSTALLATION 16 2 1 Transfer Switch 16 2 2 Unpacking 16 2 3 Mounting 16 OPERATION 16 3 1 Basic Standby Electric System 16 3 2 Standby Circuit Isolation Method 16 3 3 Total Circuit Isolation Method 17 3 4 All Transfer Switch Installations 17 3 5 Ne...

Страница 3: ...will be found within the regular text body of this manual These safety warnings cannot eliminate the hazards that they indicate Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents Four commonly used safety symbols accompany the DANGER WARNING and CAUTION blocks The type of information each indicates is as fol...

Страница 4: ...building codes Comply with regulations the Occupational Safety and Health Administration OSHA has established Also ensure that the generator is installed operat ed and serviced in accordance with the manufacturer s instruc tions and recommendations Following installation do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes standards laws and regulations Ke...

Страница 5: ...cal help Never wear jewelry when working on this equipment Jewelry can conduct electricity resulting in electric shock or may get caught in moving components causing injury FIRE HAZARDS Keep a fire extinguisher near the generator at all times Do NOT use any carbon tetra chloride type extinguisher Its fumes are toxic and the liquid can deteriorate wiring insulation Keep the extinguisher properly ch...

Страница 6: ... with applicable codes standards and regulations should install this standby electric power system The installation must comply strictly with all codes standards and regulations pertaining to the installation After the system has been installed do nothing that might render the installation in noncompli ance with such codes standards and regula tions 1 2 1 NFPA STANDARDS Applicable national state o...

Страница 7: ...l codes vary Place the pad high enough to keep rising water from reaching the generator Make sure the generator will have adequate and unob structed airflow by choosing an open space free of trees shrubs buildings or other obstructions Figure 1 1 Figure 1 1 Mounting Pad The unit must be positioned so air vents won t become clogged with leaves grass snow or debris Make sure that exhaust fumes will ...

Страница 8: ...ll phases of handling and unpacking 1 7 GENERATOR PLACEMENT Use a forklift boom truck or similar equipment with sufficient capacity to move the generator to the mounting pad area The operator should be certified and experienced in generator instal lation Figure 1 4 Figure 1 4 Lifting the Generator Before placing the generator on the pad inspect for shipping dam age and if necessary file a claim wi...

Страница 9: ...of the flexible fuel line Figure 1 8 Figure 1 8 Flexible Fuel Line After checking all connections for leaks check the static gas pressure at the secondary regulator to ensure there is sufficient pressure to operate the generator see Owner s Manual If the static pressure is too low or is higher than 14 inches of water column notify the local gas supplier Figure 1 9 Figure 1 9 Water Column 1 8 3 PRO...

Страница 10: ...vapor system at the frame of the generator are the same as those listed for natural gas in The Natural Gas System See Table 1 for information regarding the vapor capacity of LP tanks The installer should be aware of the following When ambient temperatures are low and engine fuel consump tion is high the vapor withdrawal system may not function efficiently Ambient temperatures around the supply tan...

Страница 11: ... Recommended 70kW 5 14 Water Column Recommended 70kW Figure 1 11 Typical LP Gas Vapor Withdrawal System Gas Actuator Primary Regulator Supplied by Installing Contractor 11 14 Water Column Recommended 70kW 5 14 Water Column Recommended 70kW Flex Fuel Line Supplied with Unit Generator Base Fuel Shutoff Regulator Assembly Manual Shutoff Valve Figure 1 10 Typical Natural Gas System General Information...

Страница 12: ... for Natural Gas from Equation 1 ṁ p and ṁ 91 34 lb hr p 0 0383 90 60 11111 p 0 0356 lb ft3 Thus 91 34 0 0356 And 2566 ft3 hr 1 9 2 CALCULATING PIPE SIZE Now that the volumetric flow rate has been identified the mini mum pipe size can be determined by using Table 2 This table is based on a specific gravity of 1 00 specific gravity of air For that reason a correction is required when the fuel used ...

Страница 13: ...5 750 1220 2480 3850 6500 13880 38700 79000 30 52 120 241 535 850 1780 2750 4700 9700 27370 55850 45 43 99 199 435 700 1475 2300 3900 7900 23350 45600 60 38 86 173 380 610 1290 2000 3450 6800 19330 39500 75 77 155 345 545 1120 1750 3000 6000 17310 35300 90 70 141 310 490 1000 1560 2700 5500 15800 32250 105 65 131 285 450 920 1430 2450 5100 14620 29850 120 120 270 420 860 1340 2300 4800 13680 27920...

Страница 14: ...00 40 31 60 20 51 500 119 37 46 30 0 100 150 40 35 100 20 53 850 165 41 50 50 0 105 170 40 36 120 20 51 1000 192 41 50 60 0 103 Propane storage tanks can provide either a liquid or a vapor supply to the generator The above chart is for vapor withdrawal only and provides the kW output or amount of vapor that can be withdrawn at a given temperature while keeping the temperature of the liquid above t...

Страница 15: ...al or the wiring diagram in the Owner s Manual that is supplied with the unit Figure 1 13 Battery Charger Connection 1 11 BATTERY INSTALLATION Standby generators installed with automatic transfer switches will crank and start automati cally when NORMAL UTILITY source voltage is removed or is below an acceptable preset level To prevent such automatic start up and pos sible injury to personnel do no...

Страница 16: ...arge before they are installed on the generator When using maintenance free batteries it is not necessary to check the specific gravity or electrolyte level Have these proce dures performed at the intervals specified in the Maintenance section in the Owner s Manual A negative ground system is used Battery connections are shown on the wiring diagrams Make sure all batteries are correctly connected ...

Страница 17: ...u already have your activation code wait 3 5 seconds for the next display ENTER ACTIVATION CODE Passcode TROUBLESHOOTING Display Reads Use ARROW keys to scroll and find the first num ber of your Activation Code Press ENTER to select Repeat this step until all digits have been entered Use ESCAPE to correct previous digits Display Reads Activation is complete when all digits are entered above and yo...

Страница 18: ...ition switches Because load circuits can only be connected to one power supply at a time open transition switches prevent electrical feedback between utility circuits and generator circuits Figure 2 1 Figure 2 1 Connect Power Leads 3 1 BASIC STANDBY ELECTRIC SYSTEM Figure 3 1 shows a schematic diagram of a basic standby electric system Both the UTILITY power supply and the STANDBY GEN ERATOR outpu...

Страница 19: ...alled between the utility service entrance and the building distribution panel The generator will be backing up all electrical loads within the circuit so the amperage rating of the transfer switch must be equal to or greater than the amperage rating of the normal utility service Unless a service entrance rated transfer switch is used a main service disconnect D must be located before the transfer...

Страница 20: ...re to turn OFF both the NORMAL UTILITY and STANDBY EMERGENCY power supplies before trying to connect power source and load lines to the transfer switch Supply voltages are extremely high and dangerous Contact with such high voltage power supply lines causes extremely hazardous possibly lethal electrical shock Be sure to maintain proper electrical clearanc es between live electrical parts and groun...

Страница 21: ...19 Operation Figure 3 6 Nexus to RTS Nexus Smart Switch Drawing 0H7453 C ...

Страница 22: ...T1 NEU and leads 23 and 194 Control system interconnection leads must be run in a conduit that is separate from the AC power leads Recommended wire gauge size depends on the length of the wire Max Cable Length Recommended Wire Size 460 feet 140m No 18 AWG 461 to 730 feet 223m No 16 AWG 731 to 1 160 feet 354m No 14 AWG 1 161 to 1850 feet 565m No 12 AWG 3 7 2 LOAD WIRING Power source and load line c...

Страница 23: ...5 30 20 20 25 12 10 30 35 40 25 30 35 10 8 40 50 55 30 40 45 8 6 55 65 75 40 50 60 6 4 70 85 95 55 65 75 4 3 85 100 110 65 75 85 3 2 95 115 130 75 90 100 2 1 110 160 150 85 100 115 1 1 0 125 150 170 100 120 135 1 0 2 0 145 175 195 115 135 150 2 0 3 0 165 200 225 130 155 175 3 0 4 0 195 230 260 150 180 205 4 0 250 215 255 290 170 205 230 250 300 24 285 320 190 230 255 300 350 260 310 350 210 250 28...

Страница 24: ...Part No 0H8218 Revision F 05 08 12 Printed in U S A ...

Страница 25: ......

Страница 26: ......

Отзывы: