Generac Power Systems SD350 Скачать руководство пользователя страница 3

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. Please consult a Generac Power Systems Industrial 
Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528 and DIN6271 standards.

POWER RATINGS (kW)

STARTING CAPABILITIES (sKVA)

FUEL

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

PRIME

Three-Phase 120/208VAC @0.8pf

350 kW

Amps: 1216

315 kW

Amps: 1094

Three-Phase 120/240VAC @0.8pf

350 kW

Amps: 1053

315 kW

Amps: 948

Three-Phase 277/480VAC @0.8pf

350 kW

Amps: 527

315 kW

Amps: 474

Three-Phase 346/600VAC @0.8pf

350 kW

Amps: 421

315 kW

Amps: 379

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

400

387

581

775

968

1162

1356

210

350

500

680

875

1100

Upsize 1

442

475

720

915

1145

1030

1290

-

-

-

-

-

-

Upsize 2

555

457

686

914

1143

1371

1600

-

-

-

-

-

-

Fuel Consumption Rates*

STANDBY

PRIME

Fuel Pump Lift - in (mm)

Percent Load

gph

lph

Percent Load

gph

lph

36 (900)

25%

8.4

31.8

25%

7.56

28.8

50%

14.5

54.9

50%

13.05

49.6

Total Fuel Pump Flow (Comb Return)

75%

20.1

76.1

75%

18.09

68.5

31 gph

100%

25.3

95.8

100%

22.77

86.3

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes. 

STANDBY

PRIME

Coolant Flow per Minute

gpm (lpm)

145 (552)

145 (552)

Heat Rejection to Coolant

BTU/hr

932,760

840,590

Inlet Air

 cfm (m3/min)

19,070 (539.7)

19,070 (539.7)

Max. Operating Radiator Air Temp

Fº (Cº)

122 (50)

122 (50)

Max. Operating Ambient Temperature

Fº (Cº)

104 (40)

104 (40)

Coolant System Capacity

gal (L)

16.6 (63)

16.6 (63)

Maximum Radiator Backpressure

in H

2

O

1.5

1.5

STANDBY

PRIME

Flow at Rated Power

 cfm (m3/min)

1195 (33.8)

1076 (30.4)

STANDBY

PRIME

Rated Engine Speed

rpm

1800

1800

Horsepower at Rated kW**

hp

530

477

Piston Speed

 ft/min

1770

1770

BMEP

psi

313

281

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

PRIME

Exhaust Flow (Rated Output)

 cfm (m

3

/min) 2988 (84.6)

2808 (79.5)

Max. Backpressure (Post Silencer)

inHg (Kpa)

1.5 (5.1)

1.5 (5.1)

Exhaust Temp (Rated Output)

ºF (ºC) 1076 (580)

1076 (580)

Exhaust Outlet Size (Open Set)

NPT (male)

88.9 (3.5)

88.9 (3.5)

3 of 5

SD350 

operating data (60Hz)

350 kW Diesel

Содержание SD350

Страница 1: ... STANDARDS POWER MATCHED OUTPUT 4 ENGINEERED FOR PERFORMANCE INDUSTRIAL GRADE 4 IMPROVES LONGEVITY AND RELIABILITY Alternator TWO THIRDS PITCH 4 ELIMINATES HARMFUL 3RD HARMONIC LAYER WOUND ROTOR STATOR 4 IMPROVES COOLING CLASS H MATERIALS 4 HEAT TOLERANT DESIGN DIGITAL 3 PHASE VOLTAGE CONTROL 4 FAST AND ACCURATE RESPONSE Controls ENCAPSULATED BOARD W SEALED HARNESS 4 EASY AFFORDABLE REPLACEMENT 4 ...

Страница 2: ...tem Oil Filter Type Full Flow System Voltage 24VDC Crankcase Capacity L qts 35 36 9 Battery Charging Alternator Std Battery Size at 0ºC 1155 CCA Battery Group 8D Battery Voltage 2 12VDC Ground Polarity Negative ALTERNATOR SPECIFICATIONS Standard Model 520 mm Generac Voltage Regulator Type Digital Poles 4 Number of Sensed Phases 3 Field Type Revolving Regulation Accuracy Steady State 0 25 Insulatio...

Страница 3: ...Load gph lph 36 900 25 8 4 31 8 25 7 56 28 8 50 14 5 54 9 50 13 05 49 6 Total Fuel Pump Flow Combustion Return 75 20 1 76 1 75 18 09 68 5 31 gph 100 25 3 95 8 100 22 77 86 3 Refer to Emissions Data Sheet for maximum fuel flow for EPA and SCAQMD permitting purposes STANDBY PRIME Coolant Flow per Minute gpm lpm 145 552 145 552 Heat Rejection to Coolant BTU hr 932 760 840 590 Inlet Air cfm m3 min 19 ...

Страница 4: ...el Touchscreen na Digital G 200 Paralleling Control Panel Touchscreen na Programmable Crank Limiter Std 21 Light Remote Annunciator Opt Remote Relay Panel 8 or 16 Opt 7 Day Programmable Exerciser Std Special Applications Programmable PLC Std RS 232 Std RS 485 Std All Phase Sensing DVR Std Full System Status Std Utility Monitoring Req H Transfer Switch Std 2 Wire Start Compatible Std Power Output k...

Страница 5: ... 58 132 9248 27 693 181 58 144 9551 37 946 208 58 147 11195 52 1325 278 58 147 12028 Tank Options MDEQ OPT Florida DERM DEP OPT Chicago Fire Code OPT IFC Certification CALL ULC CALL Other Custom Options Available from your Generac Industrial Power Dealer All measurements are approximate and for estimation purposes only Weights are without fuel in tank Sound levels measured at 23ft 7m and does not ...

Отзывы: