QT018
KW RATING
18
ENGINE SIZE
1.6 Liter 4 cyl. inline
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
KW
AMP
CB Size
120/240V, 1-phase, 1.0 pf
18
75
120/208V, 3-phase, 0.8 pf
18
62
70
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208 3-phase
34
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas
Propane
(
ft
3
/hr.)
(
gal/hr.)
cu ft/hr
Exercise cycle
48
0.52
19
25% of rated load
109
1.19
43
50% of rated load
165
1.80
65
75% of rated load
220
2.41
87
100% of rated load
278
3.04
110
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air)
ft
3
/min.
1,600
System coolant capacity
US gal.
2.0
Heat rejection to coolant
BTU/hr.
96,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
48
SOUND EMISSIONS IN DBA
Exercising at 7 meters
58
Full load at 7 meters
67
EXHAUST
Exhaust flow at rated output 60 Hz
cfm
125
Exhaust temp. at muffler outlet
°F
890
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
1800
HP at rated KW
60 Hz
28
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
OPERATING DATA
QT018
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby
ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.
There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without
notice.
KW rating is based on LPG Fuel and may derate with natural gas.