Installation

Automatic Transfer Switch Owner’s Manual

11

Connecting Start Circuit Wires

Control system interconnections consist of N1, N2, and
T1, and leads 23, 0, and 194 (see 

Figure 3-3

). 

NOTE: 

Generac Type TC-ER-JP power and control tray

cable can be installed as permitted by the 2017 NEC.
Type TC-ER-JP cable contains color-coded power and
control conductors.

The generator control wiring is a Class 1 signaling circuit.
Reference instruction manual of specific engine
generator for wiring connection details. Screw heads are
straight bladed and cross-bladed, and should be
tightened to 3.5 in-lb (0.4 Nm).
Recommended wire gauge sizes depend on wire length
as specified in the following chart: Consult factory if you
are operating more than one transfer switch and SACM.

 

Exception: 

Conductors of AC and DC circuits, rated

1000 volts nominal, or less, shall be permitted to occupy
the same equipment, cable, or conduit. All conductors
shall have an insulation rating equal to at least the
maximum circuit voltage applied to any conductor within
the equipment, cable, or conduit. See NEC 300.3(C)(1).

Connecting SACM

See 

Figure 3-3

The SACM can control an air conditioner

(24 VAC) directly.

Control of Air Conditioner Load

1.

Route the thermostat cable (from the furnace/
thermostat to the outdoor air conditioner unit) to the
transfer switch.

2.

Connect the wire to the terminal strip terminals
(A/C 1) on the SACM as shown in 

Figure 3-3

.

These are normally closed contacts which open
upon load shed conditions. Route thermostat wire
away from high voltage wires.

3.

If required, connect additional air conditioners to
the terminal strip terminals (A/C 2-4).

NOTE: 

These instructions are for a typical air conditioner

installation. Control of certain heat pumps and 2-stage air
conditioners may require special connections or the use
of SMMs to control the loads.

Recommended 

Wire Size

Maximum Wire Length

(One transfer switch                                         

and load shed module)

No. 18 AWG

1–115 ft (0.3–35 m)

No. 16 AWG

116–185 ft (36–56 m)

No. 14 AWG

186–295 ft (57–89 m)

No. 12 AWG

296–460 ft (90–140 m)

(000120)

Equipment damage. Verify all conductors are tightened 
to the factory specified torque value. Failure to do so 
could result in damage to the switch base.

CAUTION

Contact Ratings

A/C 1-4 

24 VAC, 1.0 Amp Max

Содержание PWRview RXEMW200A3

Страница 1: ...Entrance Model Number RXEMW200A3 SERIAL NUMBER _________________________ DATE PURCHASED ________________________ WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...r Conditioner Load 11 Auxiliary Contact 13 Fault Current Label 13 Installing PWRview Antenna 14 Connecting PWRview CTs 14 Section 4 Operation Functional Tests and Adjustments 15 Manual Operation 15 Cl...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...lusive If using a procedure work method or operating technique that the manufacturer does not spe cifically recommend verify that it is safe for others and does not render the equipment unsafe Through...

Страница 6: ...the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will result in death or...

Страница 7: ...efore working on utility connections of the transfer switch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will re...

Страница 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...inal lugs are standard The conductor size range is as follows This transfer switch is suitable for control of motors electric discharge lamps tungsten filament and electric heating equipment where the...

Страница 10: ...following NFPA 70 National Electrical Code UL 1008 Standard for Safety Automatic Transfer Switches NOTE It is essential to use the latest version of any standard to guarantee correct and current infor...

Страница 11: ...the top priorities then up to four SMMs as Priorities 5 8 Use only select A C priorities on the SACM as the top priorities then use additional SMMs as the remaining priorities A SMM can share a priori...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...l the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a rigid supporting structure To prevent switch distortion level all mou...

Страница 14: ...to handle the maximum current to which they will be subjected based on the 75 C column of tables charts etc used to size conductors The installation must comply fully with all applicable codes standar...

Страница 15: ...ductor within the equipment cable or conduit See NEC 300 3 C 1 Connecting SACM See Figure 3 3 The SACM can control an air conditioner 24 VAC directly Control of Air Conditioner Load 1 Route the thermo...

Страница 16: ...nditioner 2 E Thermostat 3 F Air Conditioner 3 G Thermostat 4 H Air Conditioner 4 I Spare Fuse Holder T1 fused Battery Charge N1 fused Utility Sense N2 fused Utility Sense 0 DC Ground 194 12 VDC 23 Tr...

Страница 17: ...ining the unit Owner s Manual and transfer switch manual operating handle The 2017 NEC requires that the short circuit current rating of the transfer equipment based on the type of overcurrent protect...

Страница 18: ...firmly to ensure a good seal 4 Insert antenna cable from PWRview monitor into the antenna carrier 5 Screw the included weatherproof antenna E onto the antenna cable until it is snug against the antenn...

Страница 19: ...an be viewed through the long narrow slot in the inside cover The top of the movable contact carrier arm is yellow to be easily identified Manual operation handle in the UP position LOAD terminals T1...

Страница 20: ...it breaker CB1 to ON or CLOSED 4 With an accurate AC voltmeter and frequency meter check the no load voltage and frequency Measure across ATS terminal lugs E1 to E2 E1 to NEUTRAL and E2 to NEUTRAL 5 W...

Страница 21: ...when the utility source power is turned OFF after a five second delay factory default setting After starting the transfer switch should connect load circuits to the standby side after a five 5 second...

Страница 22: ...sabled 5 After five 5 minutes verify A C 1 is energized and Status LED A C 1 is ON 6 After another 15 seconds verify A C 2 is energized and Status LED A C 2 is ON 7 After another 15 seconds verify Loa...

Страница 23: ...tartup procedure and connect to the Wi Fi network 3 Verify the PWRview monitor has establlished communication with the Wi Fi network through the PWRview Installer app on your smartphone Figure 4 3 PWR...

Страница 24: ...Operation 20 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 25: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 21 Section 5 Drawings and Diagrams Installation Drawings No 10000012171 150 200A SE...

Страница 26: ...TRANSFER 194 12V 0 GROUND N2 N1 T1 2 1 2 1 2 A C 4 A C 3 N2 N1 TRANSFER SWITCH SERVICE RATED ENTRANCE UTILITY SUPPLY FROM SERVICE DISCONNECT N1 N2 E1 T2 T1 E2 SERVICE ENTRANCE SWITCH INTERCONNECT NOT...

Страница 27: ...C 4 A C 3 A C 2 A C 1 N2 N1 T1 194 23 N1 N2 T1 0 23 TRANSFER 194 12V 0 GROUND N2 N1 T1 2 1 2 1 2 A C 4 A C 3 N2 N1 TRANSFER SWITCH SERVICE RATED ENTRANCE UTILITY SUPPLY FROM SERVICE DISCONNECT N1 N2...

Страница 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank...

Страница 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 31: ......

Страница 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: